ELECTRICAL INSTALLATION INSTRUCTIONS
All wiring must be performed by a licensed electrician in accordance with the national electrical code and all other applicable codes.
WARNING:
When using electrical products, basic precautions should always be observed, including the following:
1.DANGER: RISK OF ELECTRIC SHOCK
Connect only to a circuit protected by a
2.Grounding is required. The unit should be installed by a licensed electrician and grounded.
3.Install to permit access for servicing.
4.All building materials and wiring should be routed away from the pump body and heater (if equipped).
2.1 HORSEPOWER MODELS:
The whirlpool should be installed on a 120 vac, 20 amp dedicated circuit. The circuit should be
ELECTRICAL INSTALLATION | |
| SEPARATE 20 AMP GFCI |
| 120 VAC |
| WHIRLPOOL MOUNTED |
| AIR or ELECTRONIC SWITCH |
| or |
| WALL TIMER- |
WHITE | (2.1HP AIRSWITCH MODELS ONLY) |
BLACK | |
| PUMP/MOTOR |
| GND. |
ELECTRICAL DIAGRAM
READ AND FOLLOW ALL INSTRUCTIONS
(3) |