American Water Heater BCL3 85T275 6NOX MULTI-FLUE 4 Units with Vertical Storage Tank

Models: BCL3 95T199 6NOX BCL3 85T390 6NOX BCL3 85T275 6NOX

1 52
Download 52 pages 33.25 Kb
Page 47
Image 47

LEGEND

MULTI-FLUE (4 UNITS) WITH VERTICAL STORAGE TANK

WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.

PIPE T&P TO OPEN DRAIN

TEMPERATURE & PRESSURE RELIEF VALVE

PRESSURE RELIEF VALVE

CIRCULATING PUMP

TANK TEMPERATURE CONTROL

DRAIN

HOT WATER

TO FIXTURES

FULL PORT BALL VALVE

CHECK VALVE

TEMPERATURE GAGE

WATER FLOW SWITCH

47

PIPE T&P TO

PIPE T&P TO

PIPE T&P TO

OPEN DRAIN

OPEN DRAIN

OPEN DRAIN

HEATER

HEATER

HEATER

HEATER

PIPE T&P TO

 

 

 

OPEN DRAIN

 

 

 

FINISHED FLOOR

STORAGE TANK

HOT WATER

RETURN

ALT. COLD WATER

CONNECTIONCOLD WATER SUPPLY

EXPANSION

TANK

NOTES:

1.Preferred piping diagram.

2.The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.

3.Service valves are shown for servicing unit. However, local codes shall govern their usage.

4.The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).

5.The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.