Installation Requirements

Gas Supply Systems

Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate. Readings should be taken with all gas burning equipment off (static pressure) and with all gas burning equipment running at maximum rate (dynamic pressure). The gas supply pressure must be stable within 1.5” W.C. (0.37 kPa) from static to dynamic pressure to provide good performance. Pressure drops that exceed 1.5” W.C. (0.37 kPa) may cause rough starting, noisy combustion or nuisance outages. Increases or spikes in static pressure during off cycles may cause failure to ignite or in severe cases damage to appliance gas valves. If your low pressure system does NOT meet these requirements, the installer is responsible for the corrections.

High Pressure building supply systems use pressures that exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems must use field supplied regulators to lower the gas pressure to less than 14” W.C. (3.49 kPa) (1/2 PSI Gauge). Appliances require gas regulators that are properly sized for the water heater input and deliver the rating plate specified pressures. Gas supply systems where pressure exceeds 5 PSI (34.5 kPa) often require multiple regulators to achieve desired pressures. Systems in excess of 5 PSI building pressure should be designed by gas delivery professionals for best performance. Water heaters connected to gas supply systems that exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge) at any time must be equipped with a gas supply regulator.

Gas Pressure Requirements

All models require a minimum gas supply pressure of 3.5” W.C. (0.87 kPa) The minimum supply pressure is measured while gas is flowing (dynamic pressure). The supply pressure (dynamic) should never fall below 3.5” W.C. (0.87 kPa) The supply pressure should be measured with all gas fired appliances connected to the common main firing at full capacity. If the supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins to flow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized. See Supply Gas Regulator section and Gas Piping section of this manual.

The gas valve on all models has a maximum gas supply pressure limit of 14" W.C. (3.48 kPa). The maximum supply pressure is measured while gas is not flowing (static pressure).

Supply Gas Regulator

The maximum allowable gas supply pressure for this water heater is 14 inches W.C. (3.48 kPa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches W.C. (3.48 kPa) at any time. Regulators must be sized/used according to manufacturer's specifications.

If a positive lock-up regulator is required follow these instructions:

1.Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply.

2.Positive lock-up gas pressure regulator(s) should be installed no closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters) of equivalent length from the water heater’s inlet gas connection.

3.After installing the positive lock-up gas pressure regulator(s) an initial nominal supply pressure setting of 7.0” W.C. (1.74 kPa) while the water heater is operating is recommended and will generally provide good water heater operation. Some addition adjustment maybe required later to maintain a steady gas supply pressure.

4.When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit.

Power Supply

The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1.

Water Temperature Control and Mixing Valves

Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.

Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.

Feel water before bathing or showering.

Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.

Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater’s temperature setting by up to 20°F (11°C).

Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm and the physically/mentally disabled. Table 5 shows the approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken.

In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature.

Mixing valves are available at plumbing supply stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves.

Table 5.

Water Temperature

Time for 1st Degree Burn

Time for Permanent Burns

°F (°C)

(Less Severe Burns)

2nd & 3rd Degree

(Most Severe Burns)

 

 

110 (43)

(normal shower temp.)

 

 

 

 

116 (47)

(pain threshold)

 

 

 

 

116 (47)

35 minutes

45 minutes

 

 

 

122 (50)

1 minute

5 minutes

 

 

 

131 (55)

5 seconds

25 seconds

 

 

 

140 (60)

2 seconds

5 seconds

 

 

 

149 (65)

1 second

2 seconds

 

 

 

154 (68)

instantaneous

1 second

 

 

 

(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)

12

Page 12
Image 12
American Water Heater BCL3 95T199 6NOX, BCL3 85T390 6NOX, BCL3 85T275 6NOX instruction manual Installation Requirements

BCL3 95T199 6NOX, BCL3 85T390 6NOX, BCL3 85T275 6NOX specifications

American Water Heater Company has been a leader in the production of high-quality water heaters for residential and commercial use. Among their acclaimed collection are three notable models: the BCL3 85T275 6NOX, BCL3 85T390 6NOX, and BCL3 95T199 6NOX. Each of these models is meticulously designed, providing efficient heating solutions while prioritizing safety and environmental responsibility.

The BCL3 85T275 6NOX is an advanced model that offers a remarkable 275,000 BTU output, making it suitable for a variety of applications, from single-family homes to larger commercial settings. This unit features a powerful water heating capacity and is equipped with a robust heat exchanger that maximizes thermal efficiency. One of its key technological innovations is the low nitrogen oxide (NOX) emissions system, which significantly reduces harmful emissions, thereby complying with stringent environmental standards.

Similarly, the BCL3 85T390 6NOX enhances performance with a higher BTU output of 390,000. This capacity allows it to effectively serve larger facilities with higher demand for hot water. The technology behind this model includes an automatic flue damper that optimizes energy use by adjusting the airflow, resulting in improved combustion efficiency. Additionally, its durable construction ensures long service life, catering to the needs of both residential users and commercial operations.

The BCL3 95T199 6NOX, with its 199,000 BTU capacity, combines efficiency with versatility. This unit is designed for a wide range of water heating needs, providing an excellent option for both medium-sized homes and smaller commercial setups. Its unique design incorporates advanced insulation materials that help retain heat longer, thereby enhancing overall efficiency. Like its counterparts, this model is equipped with advanced NOX reduction technology, which makes it an environmentally friendly choice.

All three models share a common theme of reliability and efficiency. Their advanced control systems enable precise temperature management, allowing users to set their desired hot water temperatures with ease. Furthermore, each unit is designed with safety features such as a high-temperature limit switch and electronic ignition, ensuring safe operation.

In conclusion, the American Water Heater BCL3 series — featuring the BCL3 85T275 6NOX, BCL3 85T390 6NOX, and BCL3 95T199 6NOX — showcases the company's commitment to innovation, quality, and environmental stewardship. These models not only meet the demanding needs of consumers but also contribute to a more sustainable future with their low emissions and efficient systems. Whether for residential or commercial use, they are designed to deliver reliable performance year after year.