SPACE HEATING AND POTABLE WATER SYSTEM
Your water heater is equipped with inlet/outlet connections for use
in space h eating applications (see Figure 9). If this wat er heater
is to be used to supply both space heating and potable (drinking)
water, the instructions listed below must be fol lowed:
Be sure to follow the manual(s) shipped with the air handler or
other type heating system.
This water heater cannot be used in space heating applications
only.
This water heater is not to be used as a replacement for an
existing boiler installation.
Do not use with piping that has been treated with chromates,
boiler seal or other chemicals and do not add any chemicals to
the water heater piping
If the space heating system requires water temperatures in excess
of 120°F, a mixing valve must be installed per the manufacturer’s
instructions in the potable hot water supply to limit the risk of scald
injury.
Pumps, valves, piping and ttings must be compatible with
potable water.
A properly installed ow control valve is required to prevent
thermosiphoning. Thermosiphoning is the result of a continuous
ow of water through the air handler circuit during the off cycle.
Weeping (blow off) of the temperature and pressure relief valve
(T & P relief valve) or higher than normal water temperatures are
the rst signs of thermosiphoning.
The hot water line from the water heater should be vertical past
any mixing valve or supply line to the heating system to remove
air bubbles from the system Do not connect the water heater to
any system or components previously used with non-potable
water heating appliances when used to supply potable water.
These water heaters cannot be used in space heating applications
only.

Figure: 9

CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such
conditions as high line pressure, among others, have installed
devices such as pressure reducing valves, check valves, and back
ow preventers. Devices such as these cause the water system to
be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed
system the volume of water will grow when it is heated. As the
volume of water grows there will be a corresponding increase in
water pressure due to thermal expansion. Thermal expansion can
cause premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. This condition is not covered under the limited warranty. The
temperature-pressure relief valve is not intended for the constant
relief of thermal expansion.
A properly sized thermal expansion tank should be installed on all
closed systems to control the harmful effects of thermal expansion.
Contact a local plumbing service agency to have a thermal
expansion tank installed.
NOTE: To protect against untimely corrosion of hot and cold
wate r tti ngs, it is st rongl y rec omme nded t hat di -ele ctr ic uni ons
or couplings be installed on this water heater when co nnected
to copper pipe, see Figur e 10 also.

Figure: 10

Figure 9 and Figure 10 show the typical attachment of the water
piping to the water heater. The water heater is equipped with 3/4
inch NPT water connections for 50 gallon unit and 1 inch NPT
water connections for 75 g allon unit..
NOTE: If us ing c oppe r tub ing, sold er tu bing to an ad apt er bef ore
attaching the adapter to the water heater co nnections. Do n ot
solder the water line s directly to the water heater connections.
It will harm the dip tub e and damage the tank, T & P Valve and
Pipe Insulation (if supplie d)
Fit pipe insulation over the incoming cold water line and the hot
water line. Make sure that the insulation is against the top cover of
the heater.Fit T & P valve insulation over valve. Make sure that the
insulation does not interfere with the lever of the T & P valve.
Secure all insulation using tape.