26
POLYPROPYLENE INSTALLATIONS
The water heater has been approved to be installed with
Polypropylene vent material as shown in Table 5 and Table 6. The
approved application of single wall, non-exible, non-concentric
Polypropylene vent material is offered by two specic manufacturers
(Centrotherm ECO Systems and DuraVent Polypropylene. These
listed products must be installed by following the vent manufacturer’s
instructions. Refer to “Table 7” on Page 27 to determine the maximum
pipe length and number of elbows that can be used.
Insulation should not be used on Polypropylene venting materials.
The use of insulation will cause increased vent wall temperatures,
which could result in vent pipe failure.
Use only the adapters and vent system listed in Tables below. DO
NOT mix vent systems of different types or manufacturers. Failure
to comply could result in severe personal injury, death, or substantial
property damage.
Installations must comply with applicable national, state, and local
codes. If Polypropylene vent is not required by your local code, you
may use either PVC or CPVC pipes for your water heater that allows
non-metallic venting material installations.

Table 5

M & G Duravent PolyPro
Nominal Pipe
Diameter Flue Outlet Adapter Adapter
Connector
Ring
Connector
90 Degree
Elbow Vent Material Terminal(s)
2” 2PPS-AD PPS-PAC 2PPS-LB 2PPS-E90 2PPS
2PPS & 2PPS-BG for Exhaust;
2PPS-E90 & 2PPS-BG for Intake (Direct Vent
only)
3” 3PPS-AD PPS-PAC 3PPS-LB 3PPS-E90 3PPS
3PPS & 3PPS-BG for Exhaust;
3PPS-E90 & 3PPS-BG for Intake (Direct Vent
only)
Polypropylene vent systems do not use cement to connect the pipe
and elbow sections but use a push together gasket seal method.
Do not attempt to connect Polypropylene with sealant cement. All
vent connections MUST be secured by the vent manufacturer’s joint
connector. The installer must use a specic vent starter adapter at
the ue connection. The adapter is supplied by the vent manufacturer
to adapt to its vent system.
In order to be in full compliance with UL 1738 or ULC-S636 and to
meet the requirements of the water heater manufacturer, you must
use the metal joint connector rings, available from the Polypropylene
vent manufacturer, to stiffen the joints of 2”, and 3” diameter pipes.

Table 6

Centrotherm InnoFlue SW
Nominal Pipe
Diameter Flue Outlet Adapter Adapter
Connector
Ring
Connector
90 Degree
Elbow Vent Material Terminal(s)
2” ISAGL
0202 IAFC02 IANS02 ISELL0287 ISVL02
ISVL02 & IASPP02 for Exhaust;
ISELL0287 & IASPP02 for Intake (Direct Vent
only)
3” ISAGL
0303 IAFC03 IANS03 ISELL0387 ISVL03
ISVL03 & IASPP03 for Exhaust;
ISELL0387 & IASPP03 for Intake (Direct Vent
only)