AMX specifications Installation Sheet, RDM-2ZC Dual Zero Cross Module 2400 W, Specifications

Models: RDM-2ZC

1 2
Download 2 pages 46.78 Kb
Page 1
Image 1
Installation Sheet

Installation Sheet

RDM-2ZC Dual Zero Cross Module 2400 W

The RDM-2ZC Dual Zero Cross Module is a dual 2400 W zero-cross relay built for long term, reliable switching of electronic fluorescent ballasts, elec- tronic transformers and incandescent lamps. It is designed for use with the RDA series of enclosures, in an AMX Lighting™ modular digital dimming system. The module's 120, 240, and 277 VAC ratings are CE, UL, and C- UL approved.

Mounting points

Line in (hot)

High-voltage connections

Load out

Zero cross relay A

This module may require extra power from the AXlink connection or an external power supply connected to the control card.

Connecting the RDM-2ZC to the AMX Lighting Master

Pin 4 (GND)

Pin 3 (RLY)

Pin 2 (DIM)

Pin 1 (+12 V)

RDM-2ZC 4-pin module connector

3(-)

1 (+)

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to

the 4-pin connector on the master (black plug cover facing up).

FIG. 2 RDM-2ZC connections

Lighting Application Drawing

All neutrals are common to the Neutral block in the enclosure. Provide a separate neutral for each load.

Zero cross relay B

Low-voltage control wiring: 4-pin connector to AMX Lighting master controller

FIG. 1 RDM-2ZC

RDM-2ZC UL and C-UL Ratings

120-277 VAC, 2400 W

240/277 VAC, 2400 W

Suggested Switched Loads

Incandescent

Electronic transformers

HID ballast

Electronic and magnetic ballast

Specifications

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 7 in-lbs. (0.8 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 2.0 lbs. (0.91 kg)

BTU/hr: 300

Control current: 45 mA per relay (90 mA total) @ 12 VDC

(B) Load

(A) Load

(B) Line in (HOT)

(A) Line in (HOT)

Fluorescent Ballast

Ballast

 

Load

 

Neutral

Circuit breaker

Safety ground

panel

Neutral

RDM-2ZC Dual Zero Cross Module 2400 WLoad Connecting the RDM-2ZC to the AMX Lighting MasterLighting Application Drawing

Neon lights (cold-cathode, on/off)

FIG. 3 RDM-2ZC wiring configuration

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

Page 1
Image 1
AMX specifications Installation Sheet, RDM-2ZC Dual Zero Cross Module 2400 W, Lighting Application Drawing