Installation Sheet
RDM-HDC Heavy Duty DC Module 2400 W, 0-12 VDC
The
Caution: Pre-Installation Notes
• All Class 1 wiring must be connected to proper terminals. |
• All control wiring must be connected to proper terminals. |
• Disconnect power while installing or connecting the unit. |
• Keep top and bottom air vents clear at all times. |
• Use |
• Use field installed copper conductors. |
Mounting points
High |
| Neutral |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
voltage |
| Line in |
|
|
|
|
|
| - out (LV) | |
|
|
|
|
|
| |||||
|
| Load |
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||||
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| + out (LV) |
|
|
|
|
|
|
|
|
|
|
Relay
• All electrical ratings are for continuous duty. | |
• For indoor use only. | |
• | Test loads for shorts before connecting. |
• | This module may require extra power from the AXlink connection or an |
| external power supply connected to the control card. |
Connecting the RDM-HDC to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
GND 3
2(DIM)
1(+)
Note: The
FIG. 2 Connecting the
Lighting Application Drawings
FIG. 1
RDM-HDC UL and C-UL Ratings
•120 VAC, 50/60 Hz, 2400 W
•240/277 VAC, 50/60 Hz, 2400 W
•Control Out: 50 mA, 12 VDC sourcing/sinking
Suggested Dimmed Loads
•
•All
Neutral |
| - | Florescent Ballast |
| Ballast | ||
Line in (HOT) |
| + | |
|
| ||
|
| Load | |
|
|
| |
|
|
| Neutral |
LOAD LINE NEUT | CON |
| |
|
|
| to 300 V |
Circuit breaker |
|
|
|
panel |
|
|
|
FIG. 3 |
|
|
|
Warning: Failure to ground the ballast may cause ballast failure
Specifications
•Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)
•
•Use wires rated at 75°C (167°F)
•Torque terminals to 20
•Max. wire size: 10 AWG (4 mm²)
•Wire stripping length: 0.28" (7 mm)
•Weight: 1.3 lbs. (0.590 kg)
•BTU/hr: 150
•Control current: 150 mA @ 12 VDC