34001813EN/AE - Page 18
2. Installation
TNC upstream, TNS downstream

For separate Normal AC and Bypass AC lines from a single source

Installation with upstream IT and downstream TNS

For separate Normal AC and Bypass AC lines from a single source

Installation with upstream TT and downstream TT (with upstream differential protection)

For separate Normal AC and Bypass AC lines from the same source

The upstream differential protection rating must be at least 3A

1.the UPS internal PEN bar must be connected to the Q4S neutral upstream of Q4S

2.The UPS internal PEN bar must be connected to the Q5N neutral downstream of Q5N

3.The UPS internal PE bar must be transformed into a PEN bar (cables supplied for TNC options)