34001813EN/AE - Page 62
7. Appendices
Line current values

Input / output characteristics

Normal AC source / Bypass AC source
Load output
Rated power of each
UPS unit
Continuous input
current at U=400V
Input current at
U=400V overload =
1.25 In limited to 10
min.
Input current at
U=400V overload =
1.5 In limited to 1 min.
Input/output fuse
ratings
20 kVA 29 A 36 A 44 A 80 A
30 kVA 43 A 55 A 65 A 80 A
40 kVA 58 A 72 A 87 A 80 A
60 kVA 87 A 108 A 130 A 125 A
80 kVA 115 A 145 A 174 A 160 A
100 kVA 144 A 181 A 217 A 315 A
120 kVA 173 A 217 A 260 A 315 A
Standard UPS UPS with backfeed
protection
Uin 380 to 443 V 380 to 443 V
Input voltage range permitted by the standard
according to the curve below
250 to 470 V 340 to 470 V
Fin 45 to 65 Hz 45 to 65 Hz
Uout 380 V 400 V 415 V + 3%
- 3%

Power supplied as a function of

input voltage

Permissible UPS overloads as a function of time

P/Pn

100%
70%
250V 340V 470VU
I/In
2,2
2
1,8
1,6
1,4
1,2
110
4
1010,1 t (s)
10
5
10
3
10
2
60 600