12 - 3402230800/AC
Configuration of the JBUS/MODBUS communication parameters
Use the cord supplied with the card
Connect the card to a computer
Use a terminal emulator such as HyperTerminalTM with these settings
"Echo typed characters locally" option: disabled
Check that UPS power is on.
Type MGEUPS (or mgeups).
The main configuration menu is displayed::
Press the 5 key (Jbus configuration).
The Jbus configuration menu is displayed:
Through settings port
Bits per second Data bits Stop bits Parity Flow control
9600 8 1 none none
APC by Schneider Electric
Network Management Card & Modbus/Jbus
Release : AB.build_5_0_7
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
Jbus settings
1 : Display Jbus settings
2 : Modify Jbus settings
3 : Display Jbus diagnostics
4 : Reset Jbus diagnostics
5 : Return to Jbus Default Configuration
6 : Display Jbus frames
0 : Exit
66102
Settings/Sensor
ETHERNET
100M 10MUPS data RS232
On = Link
Blink = Act
ETHERNET
66103
UPS data RS232
100M 10M
66103
UPS data RS232
100M 10M
UPS
Connect the RS232 link to a
terminal
(Microsoft Hyper terminal)