10 Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual
Configuration Settings
Configuration Settings

Settings are adjusted through PowerChute software, optional SmartSlot accessory cards, or in terminal

mode.

Function Factory

Default

User Selectable

Choices Description

Automatic
Self-Test
Every 14 days
(336 hours)
• Every 7 days
(168 hours)
• Every 14 days
(336 hours)
• On start up only
• No self-test
Set the interval at which the UPS will execute a
self-test.
UPS ID UPS_IDEN Up to eight characters
(alphanumeric)
Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.
Date of Last
Battery
Replacement
Manufacture
Date
mm/dd/yy Reset this date when you replace the battery
module.
Minimum
Capacity Before
Return from
Shutdown
0 percent • 0%
•15%
•30%
•45%
•60%
•75%
•90%
Specify the percentage to which batteries will be
charged following a low battery shutdown before
powering connected equipment.
Alarm Delay Enable •Enable
•Mute
• Disable Mute ongoing alarms or disable all alarms
permanently.
Shutdown Delay 9 0 seconds • 0 s
•90 s
•180 s
•270 s
•360 s
•450 s
•540 s
•630 s
Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.
Low Battery
Warni ng
2 minutes •2 m
•5 m
•8 m
•11 m
•14 m
•17 m
•20 m
•23 m
PowerChute software interface provides
automatic, unattended shutdown when
approximately two minutes of battery operated
run time remains.
The low-battery warning beeps are continuous
when two minutes of run time remain.
Change the low battery warning interval setting to
the time that the operating system or system
software requires to safely shut down.
Synchronized
Turn-on De lay
0 seconds •0 s
•60 s
•120 s
•180 s
•240 s
•300 s
•360 s
•420 s
Specify the time the UPS will wait after the return
of utility power before start up (to avoid branch
circuit overload).