Configuration Settings

 

 

 

 

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

 

 

 

High Bypass

100V Models:

100V

110-120V

Maximum voltage that the UPS will pass to

Points

110V

• 107V

• 127V

connected equipment during internal bypass

 

120V Models:

• 110V

• 130V

operation.

 

133V

• 113V

• 133V

 

 

 

• 116V

• 136V

 

 

 

• 119V

• 139V

 

 

 

• 122V

• 142V

 

 

 

• 125V

• 145V

 

 

 

• 128V

• 148V

 

 

 

 

 

 

Low Bypass

100V Models:

100V

110-120V

Minimum voltage that the UPS will pass to

Points

78V

• 78V

• 86V

connected equipment during internal bypass

 

120V Models:

• 80V

• 88V

operation.

 

86V

• 82V

• 90V

 

 

 

• 84V

• 92V

 

 

 

• 86V

• 94V

 

 

 

• 88V

• 96V

 

 

 

• 90V

• 98V

 

 

 

• 92V

• 100V

 

 

 

 

 

 

Output Frequency

Automatic

Automatic

 

Sets the allowable UPS output frequency.

 

50 ± 3 Hz or

50 ± 3 Hz or

 

Whenever possible, the output frequency tracks

 

60 ± 3 Hz

50 ± 0.1 Hz

 

the input frequency.

 

 

 

 

 

60 ± 3 Hz or

 

 

 

 

60 ± 0.1 Hz

 

 

 

 

 

 

Number of Battery

1

Number of connected

Defines the number of connected battery packs

Packs

 

battery packs

 

for proper run time prediction.

 

 

 

 

1 = internal battery module,

 

 

 

 

2 = one SURT192XLBP or SURT192XLBPJ, 3 =

 

 

 

 

two SURT192XLBP or SURT192XLBPJ, etc.

 

 

 

 

 

Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual

11

Page 11
Image 11
APC 2400 VA, 990-2233A, SURTA3000XL user manual Function Factory User Selectable Description Default Choices