Terminal Mode Configuration

Avoid using extension cords when connecting equipment to and from the UPS.

1.Ensure that equipment is connected to the UPS.

2.Only use a power cord to plug the UPS into a two-pole three-wire grounded receptable.

3.Turn on all connected equipment.

4.To power up the UPS, press the button on the front panel.

For Additional Computer System Security

For additional computer system security, install PowerChute® Business Edition Smart-UPS®monitoring software. Refer to the software CD included in the literature kit for instructions.

Terminal Mode Configuration

Terminal mode can only be used with the serial cable. Connect the serial cable to the UPS before using the terminal program.

Shown below is an example of how to use terminal mode to configure the number of external battery packs. See “Configuration Settings” on page 10 for additional information.

1.Exit the PowerChute Business Edition software.

a.From the windows PC desktop, select START => Settings => Control Panel => Administrative Tools => Services.

b.Select APC PCBE Server and APC PCBE Agent. Right click the mouse and select Stop.

2.Open a terminal program. Example: HyperTerminal

a.From the computer desktop, select START => Programs => Accessories => Communication => HyperTerminal.

3.Double-click the HyperTerminal icon.

a.Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

b.Select the COM port that is connected to the UPS. The port settings are:

Bits per second - 2400

data - bits 8

parity - none

stop bit - 1

flow control - none

c.Press Enter.

4.Once the terminal window is open, follow these steps to set the number of external battery packs (SURT192XLBP or SURT192XLBPJ):

a.Press Enter to initiate terminal mode. Follow the prompts.

b.Press 1 to modify UPS settings. Press e (or E) to modify the number of battery packs.

c.Enter the number of battery packs, including the internal battery module (Number of packs: 1 = internal battery module, 2 = one SURT192XLBP or SURT192XLBPJ, 3 = two SURT192XLBP or SURT192XLBPJ, etc.)

d.Press Enter.

e.Follow the prompts.

5.Exit the terminal program.

Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual

7

Page 7
Image 7
APC SURTA3000XL, 990-2233A, 2400 VA user manual Terminal Mode Configuration, For Additional Computer System Security