Options/Accessories

6.1.3 Operating The External Service Bypass Switch

Action

 

 

 

 

1.

Press

 

on the keyboard

Display shows

 

2.

Press

 

or

on the keyboard until

Bypass operation

 

:NO

 

 

 

 

 

3.

Press

 

on the keyboard

Bypass operation

 

 

 

 

 

:YES

 

 

 

 

 

4.

Press

 

on the keyboard

Lamp indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on Service Bypass Panel

5.

Check lamp indication on the Service Bypass Panel

The Green lamp (H003)

 

 

 

 

 

above the bypass switch

 

 

 

 

 

handle (Q003) lights

6.Turn the external bypass switch (Q003) to position ”1“

7.Turn the output switch (Q002) to position ”0“

8.Open the front door and press both the green ”ON“ and the red ”OFF“ keys simultaneously

The Green lamp (H002) above the output switch handle (Q002) lights

Only the lamp (H002) above the output switch handle (Q002) lights now

Display shows

** System OFF **

The acoustic alarm sounds for 30 sec.*

9.Turn the input switch to position ”0“

The red alarm LED below the display lights and the acoustic alarm sounds for 30 sec.

* The acoustic alarm can be reset by the

key

990-4053

Installation Guide APC Silcon 480kW 400V UPS

45

Page 45
Image 45