Installation

3.0Installation

3.1Requirements on Site

All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1m free space on all sides should be allowed during installation. Once the system is installed it may be placed close to walls as long as free space is allowed for system doors to open. (Per applicable national and/or local codes.)

For ventilation and service purposes allow for free space of minimum 1m above the unit or per national and/or local codes and in front of UPS. Never install systems in direct sunlight.

NOTICE!

For reliability reasons do not stand on the UPS. keep the UPS cabinet surface free of any objects.

3.1.1 Cabinet Dimensions

UPS

Height [mm]

Width [mm]

Depth [mm]

 

 

 

 

320kW

1800

1600

800

 

 

 

 

480

1800

1900

800

 

 

 

 

Cabinet

1900 mm wide

1800 mm

1600 mm wide

1800 mm

480kW

APC Isolation

 

Transformer Module

 

320-480kW

 

990-4053

 

 

Installation Guide APC Silcon 480kW 400V UPS

7

Page 7
Image 7