Appendix
990-4053

Installation Guide APC Silcon 480kW 400V UPS 71

9.0 Appendix

9.1 Table 1. Installation Planning Data

Main Input
Breaker
Field
Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field
Wiring
Output
Breaker
*
** Internal Batteries available for 40kW units and smaller
**
Q1 Q2
Q3
* Not supplied by APC
Installation Planning Data
APC Silcon Series
AC Input Battery System DC AC Output
Min. Input Input Full INom IMax Load side Heat
Power rating Source P (kW) I (A) Cable Overcurrent Vnload Disch Disch InOvercurrent Dissipation
kW kVA Pf V Hz Nom. Max. Nom. Max. (per phase) Protection* (Vdc) P(kW) (A) (A) (A) Protection* (kW)
480 480 1 380
400
415
50/60 491.8 569.5 838.3
747.3
768.4
922.1
822.0
845.2
3//185mm21000 A 2x384 505.3 658 775 727.3
695.7
666.7
800 A 15.9
COLUMN 1a 1b 1c 1d 1e 1f 1g 1h 2a 2b 2c 2d 3a 3b 4a
NOTES 3 4 1 2 9 5, 6, 13 8 12 10 11 6, 7 13
* Provided by others