Appendix

9.0Appendix

9.1Table 1. Installation Planning Data

Q3

Service Bypass Panel

Main Input

 

 

Breaker *

 

Q1

 

Field

UPS Module

 

 

 

Wiring*

 

Output

Q2Breaker*

Field

Wiring*

Battery Bank**

*Not supplied by APC

**Internal Batteries available for 40kW units and smaller

Installation Planning Data

APC Silcon Series

 

 

 

 

 

 

 

 

 

AC Input

 

 

Battery System DC

 

AC Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. Input

Input

 

Full

INom

IMax

 

Load side

Heat

Power rating

Source

P (kW)

I (A)

Cable

Overcurrent

Vn

load

Disch

Disch

In

Overcurrent

Dissipation

kW

 

kVA

 

Pf

V

Hz

Nom.

Max.

Nom.

Max.

(per phase)

Protection*

(Vdc)

P(kW)

(A)

(A)

(A)

Protection*

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

480

 

480

 

1

380

50/60

491.8

569.5

838.3

922.1

3//185mm2

1000 A

2x384

505.3

658

775

727.3

800 A

15.9

 

 

 

 

 

400

 

 

 

747.3

822.0

 

 

 

 

 

 

695.7

 

 

 

 

 

 

 

415

 

 

 

768.4

845.2

 

 

 

 

 

 

666.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COLUMN

 

1a

1b

1c

1d

1e

1f

1g

1h

2a

2b

2c

2d

3a

3b

4a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES

 

 

 

3

4

1

2

9

5, 6, 13

8

12

10

11

 

6, 7

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Provided by others

 

 

 

 

 

 

 

 

 

 

 

 

 

 

990-4053

Installation Guide APC Silcon 480kW 400V UPS

71

Page 71
Image 71
APC 990-4053 manual Appendix, Installation Planning Data