11InRow SC Operation
General Configuration
The cooling group configuration options are set during the commissioning of the cooling units in the
cooling group.
Caution: This procedure must be performed by APC authorized personnel only. Changing
the settings incorrectly can cause malfunctions to your cooling unit.

Cooling unit configuration

Path: Main > Configure Unit > General
Use the General menu to set the following:
Start-up Delay. The delay begins when the cooling unit is started and initialized. The cooling unit
cannot begin operation until this delay expires. Use the start-up delay to restart equipment sequentially in
your room after a scheduled downtime.
Idle On Leak. When set to Yes , the cooling unit will enter idle mode if a Water Detection Fault
activates. Set to No to disable the cooling unit from entering idle mode if a leak is detected.
Note: The leak sensor (APC part number AP9325) is optional.
Note: There are three alarms that will cause the cooling unit to enter idle mode:
• Water Detection Fault (when Idle On Leak is set to Yes)
• Condensate Pump Fault
• Cooling Failure