Electrical Specifications

Attention:

Operation above the input voltage range may cause equipment damage.

Operation below the input voltage range may cause overload or automatic shutdown. When connecting directly to a branch circuit, check that the line voltage is within specifications. When connecting to the UPS, check that the line voltage into the UPS is within specifications before transferring to bypass mode.

Note: In order for AP9626 models to output the full 5000 VA, the input must be hardwired to a 5500 VA source.

Installation

With Line Cord

 

With Hardwire

 

(AP9826 or AP9627)

 

(AP9626 or AP9628)

Nominal Input Voltage

 

208 Vac

Nominal Output Voltage

 

120 Vac

Input Voltage Range

 

185-230 Vac*

Input Current Rating

24 A

 

26 A

Line Frequency

 

60 Hz

Efficiency

 

90-95%

Maximum Input Power

5000 VA

 

5500 VA

Maximum Output Power

4500 VA

 

5000 VA

 

 

 

 

*For continuous operation below Vin = 205 Vac, the output load must be reduced to limit the maximum input current to the amount specified above. Continuous operation above the maximum specified input current may cause the unit to overheat and shut down. Please contact APC for additional information.

**Not available for AP9627.

Model

AP9626

AP9627

AP9628

Input Power

3 ft cord with L6-30P or

2 ft cord with L6-30P

Hardwire

Distribution

hardwired

 

 

 

Output Power

(2) 15 A circuits with

(4)

20 A circuits with

Hardwire

Distribution

(4) 5-20R and (2) 15 A circuits

(4)

L5-20R

 

 

with (2)5-20R

 

 

 

4

APC Step-Down Transformer User Manual

Page 4
Image 4