APC AP9626, AP9628, AP9627 user manual Electrical Configuration, Hardwiring, Use 10-gauge 6 mm2 wire

Models: AP9626 AP9628 AP9627

1 10
Download 10 pages 15.55 Kb
Page 6
Image 6
Electrical Configuration

Electrical Configuration

Electrical Configuration

Attention:

The AP9626 and AP9627 models DO NOT require hardwiring. Use the attached cord to connect to utility power. For optional AP9626 hardwiring, follow wiring instructions below.

Hardwiring

Attention:

All electrical configurations must be performed by a qualified electrician.

Adhere to all local and national electrical codes.

Verify that all branch circuit (mains) are de-energized and locked out before installing cables or making connections.

Use 10-gauge (6 mm2) wire.

1.Switch the transformer input circuit breaker and the utility circuit breaker OFF.

2.Remove the access panel, by removing screws (see A for AP9626 models and B for AP9628 models).

A.B.

3.For AP9626 models only, disconnect the power cord from the terminal blocks.

4.For AP9628 models only, remove circular knockouts.

5.Install a flexible type conduit for input and output (AP9628 models only) panels, and secure.

6.Run wires through the conduit.

7.Connect the new wires to the terminal blocks (see the terminal blocks for AP9626 models and AP9628 models below). Wire to the ground block first. Each terminal block is labeled.

Input

L N

Output

L N

Input

L1 L2

8.Switch the circuit breakers ON.

9.Check line voltages.

10.Reinstall the access panel (AP9628 models), or install the new hardwire access panel (supplied with AP9626 models).

6

APC Step-Down Transformer User Manual

Page 6
Image 6
APC AP9626, AP9628, AP9627 Electrical Configuration, Hardwiring, Adhere to all local and national electrical codes