XLBP Replacement Batteries—APCRBC118

XLBP Replacement Batteries—APCRBC118

Remove the XLBP Batteries

 

 

su0574a

su0584a

su0573a

Install the XLBP Replacement Batteries

su0597a

su0596a

Reset the Battery Install Date

su0343b

Reset the Battery Install Date for the internal UPS battery.

If the Battery Install Date screen does not appear on the display interface within two minutes of installing the new battery, use the arrow keys to navigate to: Main Menu > Configuration > Battery Install Date.

On the Battery Install Date screen, use the arrow keys to select the month, date, and year. Press ENTER to make a selection and move to the next option.

When finished, press ENTER to save the date.

When the RBC is fully charged, perform a self-test and run time calibration test.