Specifications | Order Replacement Battery |
|
Input | Voltage | 230 Vrms Nominal |
| |
|
|
| ||
| Frequency | 50/60 Hz (auto sensing) | ||
|
|
|
| |
| Brownout Transfer | 180 Vrms, typical |
| |
|
|
|
| |
| 266 Vrms, typical |
| ||
|
|
|
| |
Output | Voltage On Battery | 230 Vac rms +/- 8% |
| |
|
|
| ||
| Total Amperage (8 outlets) | 10 Amps (including UPS output) | ||
|
|
|
| |
| UPS Capacity (4 outlets) | 550VA/330W | 700VA/405W | |
|
|
|
| |
| Frequency - On Battery | 50/60 Hz |
| |
|
|
| ||
| Transfer Time | 6 ms typical, 10 ms maximum | ||
|
|
|
| |
Protection | AC Surge Protection | Full time, 451 joules |
| |
and Filter |
|
|
|
|
|
|
|
| |
| Phone/fax/DSL Surge | Single line |
| |
| Protection |
|
|
|
|
|
| ||
| Network Surge Protection | |||
|
|
|
|
|
| EMI/RFI Filter | Full time |
|
|
|
|
| ||
| AC Input | Resettable circuit breaker | ||
|
|
| ||
Battery | Type | Sealed, | ||
|
|
| ||
| Average Life | 3 - 5 years depending on the number | ||
|
| of discharge cycles and | ||
|
| environmental temperature | ||
|
|
|
|
|
Physical | Net Weight | 6.4kg | 6.8kg |
|
|
|
|
| |
| Dimensions (H x W x D) | 285 x 230 x 86 mm |
| |
|
| (11.2 x 9.1 x 3.4 in) |
| |
|
|
| ||
| Operating Temperature | 0oC to 40 oC (32 oF to 104 oF) | ||
| Storage Temperature | |||
| Operating Relative | 0 to 95% | ||
| Humidity |
|
|
|
|
|
| ||
| Operating Elevation | 0 to 3000 m (0 to 10,000 ft) | ||
|
|
|
|
|
Safety/ | SKU | Approval |
|
|
Regulatory |
|
|
| |
| ||||
|
|
|
|
|
| GOST |
|
| |
|
|
|
|
|
| GS |
|
| |
|
|
| ||
| CE per | |||
|
| 1, GS, |
| |
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
| ||
| EMC Compliance | CE per | ||
|
| Tick |
|
|
|
|
|
|
|
Replace with a genuine APC battery. Replacement batteries can be ordered from www.apc.com (valid credit card required). For
Warranty
The standard warranty is 3 years from the date of purchase in the EU, 2 years outside of the EU. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with APC Technical Support. APC will ship the replacement unit once the defective unit is received by the repair department or cross- ship upon the provision of a valid credit card number. The customer pays for shipping to APC, and APC pays ground
Service
DO NOT RETURN
1.Verify the battery is connected and that the circuit breaker is not tripped.
2.If there are still problems or questions, contact APC.
3.Before contacting APC, have the purchase date, UPS model, and serial number (on bottom of unit) available.
4.If the Technical Support Representative cannot solve the problem, the representative will issue a Return Material Authorization Number (RMA#) and a shipping address.
5.Pack the unit in its original packaging. If the original packaging is not available, ask APC Technical Support about obtaining a new set. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended).
6.Write the RMA# on the outside of the package.
7.Return the unit by insured carrier to the address given to you by APC Technical Support.
APC Worldwide Customer Support
UPS Wall Installation | Technical Support | http://www.apc.com/support | |
The UPS can be installed vertically or horizontally to a wall. Use the template to assist | |||
Internet | http://www.apc.com | ||
with installation and a fastener (not included) that can support at least 6.8 kg. | |||
|
|
1.Hold the template against the wall surface and use a nail or pin to mark the center of each hole.
2.Install a fastener into the wall at the marked locations. Allow 8 mm of the fastener to protrude from the wall.
3.Install the unit on the wall, using the fasteners.
Worldwide | +1 800 555 2725 |
Australia | 1 |
European Union | 000 353 91 7020002725 |
165 mm |
(6.50 in.) |
|
© 2011 APC by Schneider Electric. APC and the APC l ogo are owned by Schneider Electric Industries |
|
S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are | 06/2011 |
property of their respective owners. |
|