Connect Sensors to Sensor Ports
This procedure applies to the following sensors, which are supported by the NetBotz 355 and connect to the sensor ports:
•Temperature Sensor (AP9335T)
•Temperature and Humidity Sensor (AP9335TH)
•NetBotz Spot Fluid Sensor (NBES0301)
•NetBotz Door Switch Sensor for Rooms and Third Party Racks (NBES0302)
•NetBotz Door Switch Sensor for APC Racks (NBES0303)
•NetBotz Dry Contact Cable (NBES0304)
•NetBotz 0-5 V Cable (NBES0305)
•NetBotz Vibration Sensor (NBES0306)
•NetBotz Smoke Sensor (NBES0307)
Connect APC and third-party sensors to the four ports labeled Sensors on the NetBotz 355.
•Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect a sensor to the cable, follow the instructions provided with the sensor and the instructions provided with the cable.
•Standard third-party 0-5 V sensors require the NetBotz 0-5 V Sensor Cable (NBES0305). To connect a sensor to the cable, follow the instructions provided with the sensor and the instructions provided with the cable.
•If a sensor cable is not long enough, use an RJ-45 coupling (provided with some sensors) and standard CAT-5 cabling to extend the cable up to 15 m (50 ft) for a Temperature/Humidity Sensor (AP9335TH) or a Temperature Sensor (AP9335T) and up to 30.5 m (100 ft) for all other supported sensors.