APC NS1435A, AR4038A manual Installing Equipment, Installing cage nuts, Removing cage nuts

Models: AR4038A NS1435A

1 28
Download 28 pages 62.04 Kb
Page 16
Image 16
Installing Equipment

Installing Equipment

This section provides information on how to install rack-mount equipment in the enclosure. The instructions provided with the equipment provide more detailed information.

Identifying one U-space on the vertical mounting flange

When installing equipment, locate the top and bottom of a U-space on the mounting flanges. Every third hole on the mounting flanges of a NetShelter enclosure is numbered to indicate the middle of a U-space. A U-space consists of one of these numbered holes and one hole directly above and below it, as shown.

7Installing cage nuts

1 U Removing cage nuts 6Manual background

5Manual background

ns0014a

Installing cage nuts

APC offers a cage nut hardware kit (AR8100) for use with square holes. Install cage nuts horizontally, with the ears engaging the sides of the square hole. Do NOT install cage nuts vertically with the ears engaging the top and bottom of the square hole.

1.Insert the cage nut into the square hole by hooking one ear of the cage nut assembly through the far side of the hole.

Note: Install the cage nuts on the interior of the vertical mounting flange.

2.Place the cage nut tool (not provided) on the other

side of the cage nut and pull to snap it into position.

Removing cage nuts

1. Remove any attached screw.

2. Grasp the cage nut and squeeze the sides to release it from the square hole.

12

NetShelter CX Enclosure: Installation and Customization

Page 16
Image 16
APC NS1435A, AR4038A manual Installing Equipment, Installing cage nuts, Removing cage nuts