Function

Factory Default Options

Description

Low Transfer

120

V:

• 97 Vac

Point

106

Vac

• 100 Vac

 

 

 

• 103 Vac

 

 

 

• 106 Vac

 

 

 

 

 

230

V:

• 196 Vac

 

208

Vac

• 200 Vac

 

 

 

• 204 Vac

 

 

 

• 208 Vac

Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.This setting may also be adjusted using the power quality setting.

Note: Use the Advanced Menus to configure this setting.

Nominal Output 120 Vac

N/A

Set the nominal output voltage of the UPS on

Voltage

 

 

battery. This is available on 230 V models

230 Vac

208-252 Vac

 

 

 

only.

Transfer

High

High, Low, Medium

Select the level of sensitivity to power events

Sensitivity

 

 

that the UPS will tolerate.

 

 

 

• High: The UPS will go on battery power

 

 

 

more often to provide the cleanest power

 

 

 

supply to the connected equipment.

 

 

 

• Low: The UPS will tolerate more

 

 

 

fluctuations in power and will go on battery

 

 

 

power less often.

 

 

 

If the connected load is sensitive to power

 

 

 

disturbances, set the sensitivity to High.

 

 

 

 

Low Battery

120 sec

Set the value in

The UPS will emit an audible alarm when the

Warning

 

seconds

remaining runtime has reached this level.

 

 

 

Date of Last

Date set at factory

Reset this date when the battery module is replaced.

Battery

 

 

 

Replacement

 

 

 

 

 

 

 

Audible Alarm

On

On/Off

The UPS will mute all audible alarms if this is

 

 

 

set to Off or when the display buttons are

 

 

 

pressed.

 

 

 

 

Battery Self-

On start-up and

• Never

The interval at which the UPS will execute a

Test Interval

every 14 days since • Start-up only

self-test.

Setting

the last test

• Frequency of test

 

 

 

(days)

 

 

 

 

Reset to Factory No

Yes/No

Restore the UPS factory default settings.

Default

 

 

 