APC SMT1500, SUM1500RMXL2U operation manual Main Outlet Group and the Switched Outlet Group

Models: SUM1500RMXL2U SMT1500

1 21
Download 21 pages 6.02 Kb
Page 12
Image 12
Main Outlet Group and the Switched Outlet Group

Main Outlet Group and the Switched Outlet Group

Overview

The Main Outlet Group and the Switched Outlet Group can be configured to independently turn off, turn on, shut down, and reboot connected equipment. (These features are not available on the 750 VA units.)

The Main Outlet Group and the Switched Outlet Group can be commanded to do the following:

Turn off: Disconnect from power immediately and restart only with a manual command

Turn on: Connect to power immediately

Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power becomes available

Reboot: Shut down and restart

In addition, the Main Outlet Group and the Switched Outlet Group can be configured to do the following:

Turn on or off in a specified sequence

Automatically turn off or shut down when various conditions occur

Note: If the Main Outlet Group and the Switched Outlet Group are not configured, all of the outlets on the unit will still provide battery back-up power.

Using the Main Outlet Group and the Switched Outlet Group

The Main Outlet Group functions as a master switch. It will turn on first when power is applied, and shut off last when there is a power outage and battery run-time has been exhausted.

The Main Outlet Group must be turned on for the Switched Outlet Group to turn on.

1.Connect critical equipment to the Main Outlet Group.

2.Connect peripheral equipment to the Switched Outlet Group.

Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery runtime can be added to a short power-off delay

If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups

Equipment that needs to reboot independently from other equipment should be added to a separate group

3.Use the Configuration menus to configure how the Switched Outlet Group will react in the event of a power outage.

Customize the Main Outlet Group and the Switched Outlet Group

Use the Control menus to change the Switched Outlet Group and the Main Outlet Group settings.

Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower

9

Page 12
Image 12
APC SMT1500, SUM1500RMXL2U operation manual Main Outlet Group and the Switched Outlet Group