| Configuration |
|
|
|
| |
Function | Factory | User Selectable | Description | |
Default | Choices | |||
|
|
|
|
|
Low Battery | 2 minutes | Brightly |
| The |
Warning |
| illuminated: | when two minutes of run time remain. | |
PowerChute |
| low battery warning | To change the default interval setting, use a | |
software interface |
| level of about | 2 minutes | pointed object such as a pen to press the |
provides automatic, |
| Dimly illuminated: | Sensitivity switch located on the rear panel | |
unattended |
| next to the green Sensitivity LED, while | ||
| low battery | |||
shutdown when |
| pressing the Test button located on the front | ||
| warning level of about | |||
approximately two |
| display. | ||
| 5 minutes |
| ||
minutes of battery |
|
| ||
|
| Change the low battery warning interval setting | ||
| No illumination: | |||
operated run time |
| |||
remains. |
| low battery warning | to the time that the operating system or system | |
| software requires to safely shut down. | |||
|
| level is about 8 minutes | ||
|
|
| ||
|
|
|
|
|
Synchronized | 0 seconds | • 0 s | • 240 s | Specify the time the UPS will wait after the |
| • 60 s | • 300 s | return of utility power before start up, to avoid | |
|
| • 120 s | • 360 s | branch circuit overload. |
|
| • 180 s | • 420 s |
|
|
|
|
|
|
High Transfer Point | 100 V models: |
|
| To avoid unnecessary use of the battery where |
| 108 Vac | • 108 Vac | • 112 Vac | utility voltage is chronically high, set the high |
|
| • 110 Vac | • 114 Vac | transfer point higher if the connected |
|
| equipment can tolerate this condition. | ||
|
|
|
| |
| 120 V models: |
|
|
|
| 127 Vac | • 127 Vac | • 133 Vac |
|
|
| • 130 Vac | • 136 Vac |
|
|
|
|
|
|
| 200 V models: | • 225 Vac | • 233 Vac |
|
| 225 Vac |
| ||
|
| • 229 Vac | • 237 Vac |
|
|
|
|
|
|
| 230 V models: |
|
|
|
| 253 Vac | • 253 Vac | • 261 Vac |
|
|
| • 257 Vac | • 265 Vac |
|
|
|
|
|
|