Installation Guide
5000RM5U 208/230 V models
208 V model:
Remove the six screws that secure the PDU/IO panel to the UPS.
Save these screws for securing the IO hardwire panels.
Disconnect the PDU/IO cables as shown in the diagram.
Ground
Wire
230 V model:
Remove the eight screws that secure the PDU/I panel to the UPS. Remove the two screws that secure the terminal block in the chassis.
Save these screws for securing the IO hardwire panels.
Disconnect the PDU/IO cables as shown in the diagram.
Ground
Wire
Secure the hardwire input and output panels (supplied), to the UPS using the four screws removed from the PDU/IO panel.
Install appropriate strain relief clamps (not supplied), to the I/O panels (supplied), as shown in the diagram.
NOTE: The input and output cables may be connected to the terminal block prior to installing the panels
Secure the terminal block and label to the UPS as shown in the diagram, using two screws (supplied).
AC Input |
|
|
Connector | AC Input | I n p u t |
|
| |
| Connector |
|
and the terminal block in the UPS.
Connect input and output wires as shown in diagram.
Primary
Ground
(Green Wire)
Input Line1 (Hot)
Connect the terminal block and UPS connectors as shown in diagram.
AC Input
Connectors
Secure the blank panel to the UPS using six screws (supplied).
Ground
Input Line2
(or Neutral)
Output Line1 | Output Line2 |
(or Neutral) |
Input
AC Input Connectors
07/2008 |