Installation Guide
2200/3000XL 120/208/230 V models
The PDU and AC input/output panels on the 2200/3000 VA
Remove the screws that secure the PDU panel to the UPS. Save these screws for securing the I/O hardwire panels. Disconnect the PDUcables as shown in the diagram.
Remove the screws that secure the I/O panel to the UPS.
Save these screws for securing the I/O hardwire panels.
Disconnect the input cable
NOTE: The input and output cables may be connected to the terminal block prior to installing the panels and the terminal block in the UPS.
Secure the hardwire input panel (supplied), to the UPS using two of the screws removed from the PDU panel.
Install appropriate strain relief clamps
(not supplied), to the input panel (not supplied), as shown in the diagram.
Secure the terminal block and label to the UPS as shown in the diagram, using two screws (supplied).
AC Input Connector
Connect input and output wires as shown in diagram.
Primary
Ground
(Green Wire)
Input Line1 (Hot)
Ground
Input Line2
(or Neutral)
Output Line1 | Output Line2 |
(or Neutral) |
Connect the terminal block and UPS connectors as shown in diagram.
AC Input
Connector
AC Input
Connector
Secure the output panel to the UPS using two screws, (screws and panel supplied).
The top edge of the blank panel fits behind the output panel. Secure the blank panel to the UPS using four screws supplied.
7/2008 |