  | User Configurable Items  | |
  | 
  | 
  | 
  | ||
Function | Factory | User Selectable | Description | ||
Default | Choices | ||||
  | 
  | ||||
  | 
  | 
  | 
  | 
  | |
Low Battery  | 2 minutes  | 2, 5, 8, 11, 14,  | 
  | PowerChute software interface provides  | |
Warning  | 
  | 17, 20, 23 minutes  | automatic, unattended shutdown when  | ||
  | 
  | 
  | 
  | approximately two minutes of battery operated  | |
  | 
  | 
  | 
  | run time remains.  | |
  | 
  | 
  | 
  | The   | |
  | 
  | 
  | 
  | when two minutes of run time remain.  | |
  | 
  | 
  | 
  | Change the low battery warning interval setting  | |
  | 
  | 
  | 
  | to the time that the operating system or system  | |
  | 
  | 
  | 
  | software requires to safely shut down.  | |
  | 
  | 
  | 
  | 
  | |
Synchronized  | 0 seconds  | • 0 s  | • 240 s  | Specify the time the UPS will wait after the  | |
  | • 60 s  | • 300 s  | return of utility power before start up (to avoid  | ||
  | 
  | • 120 s  | • 360 s  | branch circuit overload).  | |
  | 
  | 
  | |||
  | 
  | • 180 s  | • 420 s  | 
  | |
  | 
  | 
  | 
  | 
  | |
High Transfer Point  | 120 V models:  | 
  | 
  | To avoid unnecessary use of the battery where  | |
  | 127 VAC  | • 127 VAC  | • 133 VAC  | utility voltage is chronically high, set the high  | |
  | 
  | • 130 VAC  | • 136 VAC  | transfer point higher if the connected  | |
  | 
  | equipment can tolerate this condition.  | |||
  | 230 V models:  | 
  | 
  | ||
  | 
  | 
  | 
  | ||
  | 253 VAC  | • 253 VAC  | • 261 VAC  | 
  | |
  | 
  | • 257 VAC  | • 265 VAC  | 
  | |
  | 
  | 
  | 
  | 
  | |
Low Transfer Point  | 120 V models:  | 
  | 
  | To avoid unnecessary use of the battery where  | |
  | 106 VAC  | • 97 VAC  | • 103 VAC  | utility voltage is chronically low, set the low  | |
  | 
  | • 100 VAC  | • 106 VAC  | transfer point lower if the connected equipment  | |
  | 
  | can tolerate this condition.  | |||
  | 230 V models:  | 
  | 
  | ||
  | 
  | 
  | The SUA500PDRI ships ready for 230 V  | ||
  | 208 VAC  | • 196 VAC  | • 204 VAC  | ||
  | sources. When operating the UPS in 208 V  | ||||
  | 
  | • 200 VAC  | • 208 VAC  | ||
  | 
  | applications, the UPS low transfer voltage  | |||
  | 
  | 
  | 
  | ||
  | 
  | 
  | 
  | settings are adjusted through PowerChute  | |
  | 
  | 
  | 
  | software or the Network Management Card.  | |
  | 
  | 
  | 
  | The proper setting for low transfer voltage is  | |
  | 
  | 
  | 
  | 196 V.  | |
  | 
  | 
  | 
  | Refer to the PowerChute user guide or the  | |
  | 
  | 
  | 
  | Network Management Card instructions for  | |
  | 
  | 
  | 
  | setting adjustment details.  | |
  | 
  | 
  | 
  | 
  | |
Output Voltage  | 
  | 
  | 
  | 230 V models only: Sets the output voltage of  | |
230 V models  | 230 VAC  | • 220 VAC  | • 240 VAC  | the UPS while operating on battery.  | |
  | 
  | • 230 VAC  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |