Troubleshooting
Problem and/or Possible Cause | Solution | |
|
| |
All LEDs are off and the UPS is wired to input utility power | ||
|
| |
The UPS is shut down or the battery is | None: The UPS will restart automatically when utility power is restored and | |
discharged from an extended outage. | the battery has a sufficient charge. | |
|
| |
The Overload LED is illuminated and the UPS emits a sustained alarm tone | ||
|
| |
The UPS is overloaded. | The connected equipment exceeds the specified “maximum load” as defined | |
| in Specifications listed on the rating label located on the UPS. | |
| The alarm remains on until the overload is removed. Disconnect nonessential | |
| equipment from the UPS to eliminate the overload condition. | |
| The UPS continues to supply power as long as it is online and the circuit | |
| breaker does not trip; the UPS will not provide power from batteries in the | |
| event of a utility voltage interruption. | |
|
| |
The Replace Battery/Battery Disconnected LED is illuminated | ||
|
| |
The Replace Battery/Battery | Check that the battery connectors are fully engaged. | |
Disconnected LED flashes and a short |
| |
beep is emitted every two seconds to |
| |
indicate the battery is disconnected. |
| |
|
| |
Weak battery | Allow the battery to recharge for 24 hours and perform a | |
| problem persists after recharging, replace the battery. | |
|
| |
Failure of a battery | Allow the battery to recharge for 24 hours. Perform the | |
Battery/Battery Disconnected LED | confirm the replace battery condition. The alarm stops and the LED clears if | |
illuminates and the UPS emits short | the battery passes the | |
beeps for one minute. The UPS repeats | If the battery fails again, it must be replaced. The connected equipment is | |
the alarm every five hours. | ||
unaffected. | ||
| ||
|
| |
The input circuit breaker trips |
| |
|
| |
The connected equipment exceeds the | Unplug all nonessential equipment from the UPS. | |
specified “maximum load” as defined | Reset the circuit breaker. | |
in Specifications listed on the rating | ||
| ||
label located on the UPS. |
| |
|
| |
The AVR Boost or AVR Trim LEDs are illuminated | ||
|
| |
The system is experiencing very high or | Have a qualified service personnel check your facility for electrical | |
low utility voltage. | problems. If the problem persists, contact the utility company for further | |
| assistance. | |
|
|
10