Configuration

UPS Settings

Configure the settings using PowerChute software, a network management card or terminal mode.

Function

Factory Default

Options

Description

 

 

 

 

Automatic

On startup and every

• On startup and every

Set the interval at which the UPS will

Self-Test

14 days (336 hours)

7 days (168 hours)

execute self-tests.

 

there after

there after

 

 

 

 

• On startup and every 14

 

 

 

days

 

 

 

 

(336 hours) there after

 

 

 

• On startup only

 

 

 

• No self-test

 

 

 

 

 

 

UPS ID

UPS_IDEN

Use a maximum of eight

Uniquely identify the UPS, i.e. server name

 

 

alphanumeric characters to

or location for network management

 

 

define a name for the UPS.

purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when the battery module is

Battery

Date

 

 

replaced.

Replacement

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries

Before Return from

 

• 15%

• 75%

will be charged following a low-battery

Shutdown

 

• 30%

• 90%

shutdown, before sending power to

 

 

 

 

connected equipment.

 

 

 

 

 

Alarm Delay

Enable

• Enable

• Disable

Specify the delay between an event and the

Control

 

• Mute

 

alarm to avoid alarms for insignificant

 

 

 

 

events.

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 sec

• 360 sec

Specify the delay between the UPS

 

 

• 90 sec

• 450 sec

shutdown command and the actual

 

 

• 180 sec

• 540 sec

shutdown.

 

 

• 270 sec

• 630 sec

 

 

 

 

 

 

Duration of

2 minutes

• 2 min

• 14 min

Specify the number of minutes before

Low Battery

 

• 5 min

• 17 min

system shutdown, after the low battery

Warning

 

• 8 min

• 20 min

warning.

 

 

• 11 min

• 23 min

 

 

 

 

 

 

Synchronized

0 seconds

• 0 sec

• 240 sec

Specify the delay between the return of

Turn-on Delay

 

• 60 sec

• 300 sec

utility power and the UPS turns on. Set the

 

 

• 120 sec

• 360 sec

interval to avoid a branch circuit overload

 

 

• 180 sec

• 420 sec

condition.

 

 

 

 

 

High Bypass Points

100 Vac models

• 107 Vac

• 119 Vac

Maximum voltage that the UPS will pass to

 

110 Vac

• 110 Vac

• 122 Vac

connected equipment during internal bypass

 

 

• 113 Vac

• 125 Vac

operation.

 

 

• 116 Vac

• 128 Vac

 

 

 

 

 

 

 

120 Vac models

• 127 Vac

• 139 Vac

 

 

133 Vac

• 130 Vac

• 142 Vac

 

 

 

• 133 Vac

• 145 Vac

 

 

 

• 136 Vac

• 148 Vac

 

SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U