Configuration
UPS Settings
Configure the settings using PowerChute software, a network management card or terminal mode.
Function | Factory Default | Options | Description | |
|
|
|
| |
Automatic | On startup and every | • On startup and every | Set the interval at which the UPS will | |
14 days (336 hours) | 7 days (168 hours) | execute | ||
| there after | there after |
|
|
|
| • On startup and every 14 |
| |
|
| days |
|
|
|
| (336 hours) there after |
| |
|
| • On startup only |
| |
|
| • No |
|
|
|
|
|
| |
UPS ID | UPS_IDEN | Use a maximum of eight | Uniquely identify the UPS, i.e. server name | |
|
| alphanumeric characters to | or location for network management | |
|
| define a name for the UPS. | purposes. | |
|
|
|
|
|
Date of Last | Manufacture | mm/dd/yy |
| Reset this date when the battery module is |
Battery | Date |
|
| replaced. |
Replacement |
|
|
|
|
|
|
|
|
|
Minimum Capacity | 0 percent | • 0% | • 60% | Specify the percentage to which batteries |
Before Return from |
| • 15% | • 75% | will be charged following a |
Shutdown |
| • 30% | • 90% | shutdown, before sending power to |
|
|
|
| connected equipment. |
|
|
|
|
|
Alarm Delay | Enable | • Enable | • Disable | Specify the delay between an event and the |
Control |
| • Mute |
| alarm to avoid alarms for insignificant |
|
|
|
| events. |
|
|
|
|
|
Shutdown Delay | 90 seconds | • 0 sec | • 360 sec | Specify the delay between the UPS |
|
| • 90 sec | • 450 sec | shutdown command and the actual |
|
| • 180 sec | • 540 sec | shutdown. |
|
| • 270 sec | • 630 sec |
|
|
|
|
|
|
Duration of | 2 minutes | • 2 min | • 14 min | Specify the number of minutes before |
Low Battery |
| • 5 min | • 17 min | system shutdown, after the low battery |
Warning |
| • 8 min | • 20 min | warning. |
|
| • 11 min | • 23 min |
|
|
|
|
|
|
Synchronized | 0 seconds | • 0 sec | • 240 sec | Specify the delay between the return of |
| • 60 sec | • 300 sec | utility power and the UPS turns on. Set the | |
|
| • 120 sec | • 360 sec | interval to avoid a branch circuit overload |
|
| • 180 sec | • 420 sec | condition. |
|
|
|
|
|
High Bypass Points | 100 Vac models | • 107 Vac | • 119 Vac | Maximum voltage that the UPS will pass to |
| 110 Vac | • 110 Vac | • 122 Vac | connected equipment during internal bypass |
|
| • 113 Vac | • 125 Vac | operation. |
|
| • 116 Vac | • 128 Vac |
|
|
|
|
|
|
| 120 Vac models | • 127 Vac | • 139 Vac |
|
| 133 Vac | • 130 Vac | • 142 Vac |
|
|
| • 133 Vac | • 145 Vac |
|
|
| • 136 Vac | • 148 Vac |
|
SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac | 7 |