Specifications

Temperature

Operating

0° to 40° C (32° to 104° F)

 

 

Storage

-15° to 45° C (5° to 113° F)

 

 

charge UPS battery every six months

 

 

 

 

 

Maximum

Operating

3,000 m (10,000 ft)

Elevation

 

 

Storage

15,000 m (50,000 ft)

 

 

 

Humidity

0% to 95% relative humidity, non-condensing

This unit is intended for indoor use only. Select a location sturdy enough to handle the weight.

Do not operate UPS where there is excessive dust or temperature or humidity are outside specified limits.

This unit has side air vents. Allow adequate space for proper ventilation.

Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.

Installation

Units may vary in appearance from those depicted in this manual. Always place UPS above XLBPs in rack-mount configuration. The unit is heavy. Remove the battery prior to installation.

Prior to connecting utility or battery power to the UPS connect the transient voltage surge-suppression (TVSS) screw.

Rack-Mount and Stack Configurations

Refer to the installation guide supplied with the rail kit for rack-mount configuration instructions.

Tower Configuration

The UPS is shipped with stabilizer brackets installed. Do not remove the stabilizer brackets when the UPS is to be operated in tower configuration. Removal of the stabilizer brackets for tower configuration may result in personal injury or equipment damage.

External Battery Pack(s)

Refer to the user manual supplied with the external battery pack for installation instructions.

SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U

5

Page 7
Image 7
APC 1500RMXL2U, SURTA2200RMXL2U Installation, Specifications, Rack-Mount and Stack Configurations, Tower Configuration