
  | PROBLEM AND POSSIBLE  | 
  | SOLUTION  | |||
  | 
  | CAUSE  | 
  | 
  | ||
THE OVERLOAD LED IS LIT AND THE UPS EMITS A SUSTAINED ALARM TONE  | ||||||
The UPS is overloaded.  | 
  | The connected equipment exceeds the specified “maximum load” as de-  | ||||
  | 
  | 
  | 
  | 
  | 
  | fined in Specifications at the APC web site, www.apc.com.  | 
  | 
  | 
  | 
  | 
  | 
  | The alarm remains on until the overload is removed. Disconnect nonessen-  | 
  | 
  | 
  | 
  | 
  | 
  | tial equipment from the UPS to eliminate the overload.  | 
  | 
  | 
  | 
  | 
  | 
  | The UPS continues to supply power as long as it is online and the circuit  | 
  | 
  | 
  | 
  | 
  | 
  | breaker does not trip; the UPS will not provide power from batteries in the  | 
  | 
  | 
  | 
  | 
  | 
  | event of a utility voltage interruption.  | 
  | 
  | 
  | 
  | 
  | 
  | If a continuous overload occurs while the UPS is on battery, the unit turns  | 
  | 
  | 
  | 
  | 
  | 
  | off output in order to protect the UPS from possible damage.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
THE REPLACE BATTERY LED IS LIT  | 
  | |||||
Replace Battery LED flashes  | 
  | Check that the battery connectors are fully engaged.  | ||||
and short beep is emitted every  | 
  | 
  | ||||
two seconds to indicate the  | 
  | 
  | ||||
battery is disconnected.  | 
  | 
  | ||||
Weak battery.  | 
  | Allow the battery to recharge for 24 hours. Then, perform a   | ||||
  | 
  | 
  | 
  | 
  | 
  | problem persists after recharging, replace the battery.  | 
Failure of a battery   | 
  | The UPS emits short beeps for one minute and the replace battery LED  | ||||
  | 
  | 
  | 
  | 
  | 
  | illuminates. The UPS repeats the alarm every five hours. Perform the self-  | 
  | 
  | 
  | 
  | 
  | 
  | test procedure after the battery has charged for 24 hours to confirm the  | 
  | 
  | 
  | 
  | 
  | 
  | replace battery condition. The alarm stops and the LED clears if the bat-  | 
  | 
  | 
  | 
  | 
  | 
  | tery passes the   | 
  | 
  | 
  | 
  | 
  | 
  | |
THE SITE WIRING FAULT LED IS LIT  | ||||||
The site wiring LED is lit  | 
  | 
  | 
  | The UPS is plugged into an improperly wired utility power outlet. Wiring  | ||
  | 
  | 
  | faults detected include missing ground,   | |||
  | ||||||
(rear panel).  | 
  | overloaded neutral circuit. Contact a qualified electrician to correct the  | ||||
120V models only. | 
  | building wiring.  | ||||
  | 
  | 
  | 
  | |||
THE INPUT CIRCUIT BREAKER TRIPS  | ||||||
The plunger on the circuit  | 
  | Reduce the load on the UPS by unplugging equipment and press the  | ||||
breaker (located above the input  | 
  | plunger in.  | ||||
cable connection) pops out.  | 
  | 
  | ||||
  | 
  | 
  | 
  | |||
  | 
  | |||||
AVR BOOST OR AVR TRIM LEDS LIGHT  | ||||||
AVR Boost or Trim LEDs light  | 
  | Have qualified service personnel check your facility for electrical prob-  | ||||
Your system is experiencing  | 
  | lems. If the problem continues, contact the utility company for further  | ||||
  | assistance.  | |||||
excessive periods of low r high  | 
  | |||||
  | 
  | |||||
voltage.  | 
  | 
  | ||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
12