APC UTS10BI, UTS6H, BU154A Circuit Maximum Time Off and Minimum Time On, Circuit Security Mode

Models: BU154A UTS6H UTS10BI UTS6

1 18
Download 18 pages 19.91 Kb
Page 13
Image 13
Circuit Maximum Time Off and Minimum Time On

Circuit Maximum Time Off and Minimum Time On

This setup option requires that Load Shedding and Time Management under System Setup, be set to ON. Once Load Shedding and Time Management have been enabled each circuit can be set individually for specific maximum time off and minimum time on. These settings will depend on the requirements of the load each circuit supports.

Maximum Off controls the allowable time for a load to be without power, after being shed during ALM operation.This prevents overload conditions.

Minimum On controls the amount of time a circuit must receive power before it is eligible to be shed to prevent an overload condition.

It is recommended that a refrigerator should have a Minimum On setting of 45 minutes to ensure adequate cooling time of contents.

CKT1 MAX TIME OFF: 1-60MIN

CKT1 MIN TIME ON: 1-60MIN

Circuit Security Mode

The factory default setting is OFF. This setup option is intended specifically for use with a specified lighting circuits. Selecting YES, enables Circuit Security Mode. The UTS will automatically cycle power to the designated circuits for two hours on and two hours off.

CKT1 SECURITY MODE: OFF

Circuit Amp Rating

Warning: This setup option should be configured by a qualified electrician during the initial setup and installation of the UTS.

Adhere to all national and local electrical codes when setting the Amp ratings for the UTS circuits. Failure to comply with electrical codes could result in UTS malfunction and damage.

The factory default setting is 15 Amps. The Amps for each circuit on the UTS should be set to match the Amp rating of the supporting circuit on the building circuit breaker panel.

CKT1 AMP RATING: 15 AMPS

12

Operation Manual Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI

Page 13
Image 13
APC UTS10BI, UTS6H, BU154A Circuit Maximum Time Off and Minimum Time On, Circuit Security Mode, Circuit Amp Rating