APC BU154A, UTS10BI, UTS6H Problem and Possible Cause, Solution, Backup2 Power Source is set

Models: BU154A UTS6H UTS10BI UTS6

1 18
Download 18 pages 19.91 Kb
Page 15
Image 15
Backup2 Power Source is set

Problem and Possible Cause

Solution

Problem: While operating on backup power the UPS repeatedly experiences an overload condition causing the circuit breaker to trip

Cause: The UPS power rating is set too

Refer to System Setup: Backup2 Power Rating in this manual.

high causing an overload condition.

 

 

 

Cause: The UPS Surge Overload

Refer to System Setup: UPS Surge Overload Delay Time in this manual.

Delay Time is set too high.

 

 

 

Cause: The UPS is experiencing a low

• The UPS batteries recharge during normal UPS operation. Refer to the UPS

battery condition.

user manual or go to the APC Web site, www.apc.com. for battery recharge

 

times.

 

• The UPS batteries may need to be replaced. Refer to the UPS user manual

 

or go to the APC Web site, www.apc.com for replacement battery

 

information.

 

 

Problem: The UPS operates on battery power while the generator is running

Cause: The UPS is not receiving

Check that the UPS is securely connected to the Convenience Outlet on the

power.

UTS.

 

 

 

 

 

 

Cause: The Voltage Sensitivity for

• Refer to System Setup: Voltage Sensitivity in this manual. The sensitivity

Backup2 Power Source is set

setting should be Medium or Low.

incorrectly.

 

 

 

 

 

 

 

 

 

 

 

Problem: The LCD displays the message

 

 

 

 

 

 

 

 

CKTX FAULT CONDITION

 

 

 

 

 

 

 

 

NO OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cause: The circuit breaker may be

• Reset the circuit breaker.

tripped.

• Check the current rating for the circuit. Refer to Circuit Setup: Circuit

 

Amp Rating in this manual. NOTE: Properly configuring the Amp

 

rating requires the services of a qualified electrician.

 

 

 

 

 

 

Cause: The fuse for the circuit breaker

Replace the fuse, and reset the circuit breaker. NOTE: Replacing a fuse

may be blown.

requires the services of a qualified electrician.

 

 

 

 

 

 

Problem: The UPS does not supply power to Circuit1

Cause: The UPS is not connected to circuit1.

Circuit1 is intended for use with utility or generator power ONLY.