Problem and Possible Cause
Solution
Problem: While operating on backup power the UPS repeatedly experiences an overload condition causing the circuit breaker to trip
Cause: The UPS power rating is set too | Refer to System Setup: Backup2 Power Rating in this manual. |
high causing an overload condition. |
|
|
|
Cause: The UPS Surge Overload | Refer to System Setup: UPS Surge Overload Delay Time in this manual. |
Delay Time is set too high. |
|
|
|
Cause: The UPS is experiencing a low | • The UPS batteries recharge during normal UPS operation. Refer to the UPS |
battery condition. | user manual or go to the APC Web site, www.apc.com. for battery recharge |
| times. |
| • The UPS batteries may need to be replaced. Refer to the UPS user manual |
| or go to the APC Web site, www.apc.com for replacement battery |
| information. |
|
|
Problem: The UPS operates on battery power while the generator is running
Cause: The UPS is not receiving | Check that the UPS is securely connected to the Convenience Outlet on the | |||||
power. | UTS. | |||||
|
|
|
|
|
| |
Cause: The Voltage Sensitivity for | • Refer to System Setup: Voltage Sensitivity in this manual. The sensitivity | |||||
Backup2 Power Source is set | setting should be Medium or Low. | |||||
incorrectly. |
|
|
|
|
| |
|
|
|
|
|
| |
Problem: The LCD displays the message |
|
|
|
| ||
|
|
|
| |||
CKTX FAULT CONDITION | ||||||
|
|
|
|
| ||
|
|
| NO OUTPUT |
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
Cause: The circuit breaker may be | • Reset the circuit breaker. | |||||
tripped. | • Check the current rating for the circuit. Refer to Circuit Setup: Circuit | |||||
| Amp Rating in this manual. NOTE: Properly configuring the Amp | |||||
| rating requires the services of a qualified electrician. | |||||
|
|
|
|
|
| |
Cause: The fuse for the circuit breaker | Replace the fuse, and reset the circuit breaker. NOTE: Replacing a fuse | |||||
may be blown. | requires the services of a qualified electrician. | |||||
|
|
|
|
|
|
Problem: The UPS does not supply power to Circuit1
Cause: The UPS is not connected to circuit1.
Circuit1 is intended for use with utility or generator power ONLY.
14 | Operation Manual Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI |