APC UTS6H, UTS10BI, BU154A operation manual Generator Start Mode, Backup2 Source Type

Models: BU154A UTS6H UTS10BI UTS6

1 18
Download 18 pages 19.91 Kb
Page 10
Image 10
Generator Start Mode

Generator Start Mode

For generators featuring manual start, use the MANUAL setting. Press the down or up arrow key to change to AUTO setting.

A warning message appears on the LCD. Wait a few seconds and another message appears on the LCD asking for confirmation that the generator is located outdoors. Use the down or up arrow keys to select YES or NO.

A UTS Hardwire Interface Kit for connecting the generator outside the house is available through your dealer or APC, www.apc.com.

GEN START MODE:

MANUAL

GEN EXHAUST CAN KILL START GEN OUTDOORS..

CONFIRM GEN OUTDOORS: NO

WARNING: Home generator backup systems should be installed by a qualified electrician.

Locate the generator outside a building and at least 10 feet away from buildings, windows, and doors.

Failure to follow this safety rule may result in illness or death from breathing carbon monoxide.

The generator must have three to four feet of space around all sides and the top to ensure proper ventilation.

Locate the generator on a dry, level surface protected from rain and excessive dust.

Fuel for gas operated generators must be stored in approved containers, and in well ventilated conditions.

Refer to the generator user documentation for additional safety precautions.

For generators featuring automatic start, use the AUTO setting.

The UTS has a remote automatic start/stop function for use with generators having the following features:

automatic start

automatic choke

remote start/stop capability

Refer to the documentation in the Generator Automatic Start/Stop Kit for automatic generator configuration instructions.

Backup2 Source Type

The factory default setting is UPS. The backup2 power source inlet, located on the

 

 

 

front of the UTS is labeled UPS Inlet as a UPS is the preferred backup2 power

 

BACKUP2 SOURCE TYPE:

 

source.

 

 

UPS

 

The system setup has three options for backup power:

 

 

 

 

 

 

Generator

 

 

• UPS (recommended BACKUP2 power source)

 

 

Other

 

 

Use the down/up arrow keys to select the preferred backup power source.

 

 

NOTE: It is recommended that a UPS be used as BACKUP2 SOURCE TYPE. A UPS provides continuous battery backup power during utility brownouts, sags, surges, and power outages.

Without the use of a UPS, fully automatic operation of the UTS cannot be guaranteed.

If a UPS is not selected for the BACKUP2 power source be sure that the UNINTERRUPTIBLE option under Circuit Setup Option 2 is not selected.

Operation Manual Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI

9

Page 10
Image 10
APC UTS6H, UTS10BI, BU154A operation manual Generator Start Mode, Backup2 Source Type