FLOAT SWITCH
If the Model 1700 is installed in an attic, the unit should be placed in a drain pan with a normally closed condensate overflow safety switch (also known as a float switch). The float switch should be wired to the float switch terminals on the dehumidifier control board. See Figure 18. Remove the jumper at the float switch terminals. The compressor is disabled when the float switch is open. The Model 1700 will continue to ventilate when the float switch is open.
FIGURE 18
LOW VOLTAGE NORMALLY
CLOSED FLOAT SWITCH
SWITCH | FLOAT |
SENSOR | ODT |
DIP SWITCH DEFINITIONS
MODEL 70 – OFF/ON (SYSTEM SETUP SWITCH #1):
Determines use of internal RH and temperature sensor or use of the RH and temperature sensor on the Living Space Control (Model 70).
MODEL
MODEL
Default is MODEL
HVAC FAN – OFF/ON (SYSTEM SETUP SWITCH #2):
Determines if the HVAC fan activates during a call for dehumidification.
HVAC
HVAC
Default is HVAC
WHL HOUSE / CONVERTIBLE (SYSTEM SETUP SWITCH #3):
Determines when the dampers are powered open or closed.
CONVERTIBLE position. The damper (DEH) terminals are actuated when the HVAC equipment is making a call for heat, cool or fan and the dehumidifier is making an internal blower call for air sampling or dehumidification.
WHL HOUSE position. The damper (DEH) terminals are actuated any time the dehumidifier is making an internal blower call for air sampling or dehumidification.
The default position is WHL HOUSE.
Determines if ventilation is restricted based on outdoor temperature
The default position is