8. CHECK HEATING OPERATION

Notes:

To avoid the minimum on and off times during system checkout, always start and end the check out procedure in the OFF mode.

Do not operate heat pumps in the heating mode at high outdoor temperatures for extended periods of time.

1. Set the thermostat to the OFF mode.

2.Set the thermostat to the HEAT mode.

With the O/B configuration setting in the B position (ON), the O/B terminal will be on in the Heat mode. In the O position (OFF), the O/B terminal will not be on in the Heat mode.

3.Raise the temperature setting above the room temperature to activate the desired stages of heating. The mode display will change from “HEAT MODE” to “HEATING”, which will flash, when the thermostat is calling for heat. Fifteen (15) seconds must elapse between each stage. Verify the correct outputs are on according to the configuration settings shown below:

TROUBLESHOOTING – HEATING OPERATION

Symptom

Cause

 

 

Thermostat does not call for heat

Minimum-off times. Change the mode to OFF first, then change the mode to

HEAT and make a call for heat.

 

 

 

Heating does not come on at all

RH terminal not connected – see wiring diagrams.

 

Heating equipment power not on.

 

 

 

 

High Balance point limit – set balance point to OFF during system checkout.

Auxiliary Heat does not come on

 

Number of Auxiliary Heat stages not set correctly. See Step 4 of Thermostat

 

Start Up (page 27).

 

Single/Multi

Multi

Multi

Single

Single

Multi

Multi

Single

Single

Configuration

HP/HC

HC

HC

HC

HC

HP

HP

 

HP

 

HP

Settings

Elect/Gas

Elect

Gas

Elect

Gas

Elect

Gas

 

Elect

 

Gas

 

Aux. Ht. Stages

 

 

 

 

 

 

1

 

2

1

 

2

 

1st Stage Heat

W1

W1

W1

W1

Y1

Y1

Y1

 

Y1

Y1

 

Y1

 

G

 

G

 

G

G

G

 

G

G

 

G

 

 

 

 

 

 

 

 

W1

W1

W1

W1

Y1

Y1

Y1

 

Y1

W1

 

W1

Outputs

2nd Stage Heat

W2

W2

W2

W2

Y2

Y2

W1

 

W1

 

 

 

 

G

 

G

 

G

G

G

 

G

 

 

 

Energized

 

 

 

 

 

 

 

 

 

 

 

 

Y1

 

 

 

Y1

 

 

W1

 

 

 

 

 

 

 

 

 

 

 

 

3rd Stage Heat

 

 

 

 

Y2

 

 

 

W1

 

 

W2

 

 

 

 

 

W1

W1

 

 

W2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

G

 

 

G

 

 

 

 

Furnace plenum sensor keeps fan on – normal.

Fan stays on after heat call

Blower Extension for humidifier operation. Verify that the message

"HUMIDIFYING" appears at the message center, alternating with the time

 

 

and date and any other currently active messages.

 

 

Fan comes on before heat starts, or

Change position of ELECT/GAS dip switch – ELECT for electric heat systems

(fan on with heat call) or to GAS for fossil fuel systems where the fan is

Fan does not come on with heat

controlled internally by the heating equipment.

 

Cooling comes on instead of heat

O/B dip switch not set properly. See Step 2, page 30.

 

Miswiring – check wire colors at thermostat and HVAC equipment.

 

Takes longer than 15 seconds for auxiliary

SINGLE/MULTI dip switch set incorrectly – set to SINGLE for single-stage

heat to come on after compressor heat.

compressor systems.