(11) CUSTOMIZE THE APPLICATION SETTINGS

2. DIFFERENTIALS

Determines the temperature above/below the temperature setting at which the heating or cooling equipment will turn

3. Use the ▲ or ▼ button to highlight “SET DIFFERENTIAL”

and press the SELECT button.

– If the thermostat SINGLE/MULTI dip switch is set for

1. PROGRAMMABLE OR NON-PROGRAMMABLE

This thermostat can be configured as a programmable or non-programmable thermostat. Four choices are available:

4-Residential

This setting is best for homeowners where there

 

are regularly scheduled, long periods of time

 

during any day where the house is not occupied,

 

such as when everyone is at school or work. In

 

the program, there will be four scheduled

 

temperature changes per day (events) labeled

 

Wake, Leave, Return and Sleep.

2-Residential

This setting is best for homeowners who have

 

no long periods of time during the day when the

 

home is unoccupied. In the program, there will

 

be only two scheduled temperature changes per

 

day (events) labeled Day and Night.

2-Business

This setting is best for businesses that are

 

occupied during business hours and not occupied

 

during non-business hours. In the program, there

 

will be only two scheduled temperature changes

 

per day (events) labeled Occupied and Unoccupied.

0-Non Programmable This setting is best when having the temperature setting change with the time of day is not desired. The Program option in the menu is not available when this setting is selected. To change the temperature, simply use the Up and Down arrow buttons.

1.Make sure the thermostat is in the OFF mode.

2.Press MENU button to show the MAIN MENU.

3.Scroll down through the menu items and select SETTINGS.

4.In the SETTINGS MENU, scroll down through the menu items and select EVENTS PER DAY.

5.To cancel, press the BACK button. This will return you to the

SETTINGS MENU.

6.To change, use the ▲ or ▼ button to scroll to the desired setting.

7.To finish and return to the SETTINGS MENU, press the SELECT button.

on. For example, a heat temperature setting of 70°F with a differential of 2° will result in the equipment turning on and off to maintain the temperature between 68°F and 70°F. If the second stage differential is also 2°, the second stage would be used to ensure the temperature did not drop below 66°. The default setting for the first stage and second stage differential is 1°.

To change the differential settings:

1.Make sure the thermostat is in the OFF mode.

2.Press and hold both the ▲ and ▼ buttons for 3 seconds.

– The display will show the ADV. SETTINGS MENU.

 

MULTI, two differentials will appear, if set for SINGLE,

 

only one will appear.

4.

To cancel, press the BACK button. This will return you

 

to the ADV. SETTINGS MENU.

5.

To change the first stage differential, press the ▲ and ▼

 

button to raise or lower the setting. To change the second

 

stage differential, press the SELECT button.

6.

To finish and return to the ADV. SETTINGS MENU, press

 

the SELECT button after the value(s) have been set.

 

For heat pumps – the auxiliary heat differential(s) are

 

set separately after the number of auxiliary heat stages is

 

selected. See Diagrams 6-8on pages 14 -16 for auxiliary

 

heat set up instructions.