AquaPRO PRO1100e Troubleshooting, Guide cont, Unit is not running All Models, Unit will not cool

Models: PRO1100e PRO1300 TCE PRO1300 PRO1100 PRO1100e TCE PRO1300h/c TCE PRO1300h/c

1 28
Download 28 pages 32.19 Kb
Page 13
Image 13
Troubleshooting

PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE

Troubleshooting

Guide (cont.)

FS: This code has the following sequence:

When first displayed, the unit has started the defrost cycle and will reverse operation for 2 minutes. If unit is at acceptable temperature after the defrost cycle, it will go back into heating mode.

If coolant temperature is still too low after the initial 2 minute defrost cycle, unit will shut off the compressor and run only the fan for 60 minutes. If unit is at acceptable temperature after the 60 minutes, it will go back into heating mode.

If coolant has not reached the desired temperature after the 60 minutes, fan only mode, unit will shut down and display “FS”.

Unit will resume normal operation after ambient temperature reaches acceptable operating temperature.

MODELS: PRO1100e TCE, PRO1300 TCE and PRO1300h/c TCE

FL3: This code means that water flow was lost. Check the system for flow obstructions.

Unit is not running (All Models):

Check the power light. Check to see if the breaker is set.

Make sure the filtration system is on

Make sure the thermostat is higher than the pool water temperature

Make sure the filter is clean and is allowing enough water to flow

Make sure the outside ambient temperature is higher than 50ºF (38°F for h/c units)

Make sure the 5-minute time delay has passed

FOR TCE UNITS

Make sure time setting, in “FIL” mode, is not set to “OFF”.

Unit is running but not heating:

Check the air coming out of the top of the unit. It should be approximately 8ºF - 15ºF lower than the surrounding ambient air temperature. If not, call AquaPRO® Systems for service.

Unit will not cool:

FOR h/c UNITS:

Make sure P-S is set to “POL” mode as unit will not cool in “SPA” mode.

Unit runs continuously:

It may be running continuously because it cannot reach the desired temperature.

Lower the temperature setting below the pool water temperature. Unit should turn off. If the unit is still running, call AquaPRO® Systems for service.

A pool blanket may be required to help reach this temperature. Also, the filter pump may need to run longer for the heater to reach the desired temperature.

FOR TCE UNITS

Make sure the setting is not set to “ON” position in the “FIL” mode.

Unit is cycling:

Check the filters for proper water flow

Check the evaporator coil for severe frost

Unit could be low on refrigerant. At this point, call AquaPRO® Systems for service and turn off the power to the heater to keep the cycling from damaging the compressor.

www.aquaprosystems.com