VENTING

WARNING: Do not reduce the vent pipe size and do not common vent with any other vented appliance or stove.

This appliance must be vented horizontally to the outside with a sealed 4” single wall vent pipe. The appliance’s flue gasses are under positive pressure and must travel through a single wall 4” pipe that is sealed gas tight. The 4” single wall vent pipe can be either stainless steel (AL29-4C) or galvanized steel with at least 26 gauge. CEC recommends the use of stainless steel vent pipe (which is equipped with sealing gaskets) for ease of installation and durability. When using galvanized vent pipe a minimum of 4 sheet metal screws per connection must be installed and all seams must be sealed with an approved high temperature silicone sealant. The vent system must be gas tight. See Fig. 4 for suggested venting installation diagrams.

The 125FX shall not be vented in combination with any other appliance. This appliance may only be vented horizontally with a dedicated sealed single wall vent. The 125FX shall not be vented into masonry chimneys or existing vertical vents of any material.

CAUTION: 125FX vent system must be installed by a qualified agency in accordance with these instructions. If improperly installed a hazardous condition such as explosion or Carbon Monoxide poisoning could result. Controlled Energy Corporation will not be responsible for improperly installed appliances.

Establish vent clearances that comply with vent manufacturer’s specifications. In all cases follow local codes. See table below.

The vent diameter must be 4”. The appliance should be located as close to the point of termination as possible (see Fig. 5 for locating the terminator). The vent system should be as straight and short as possible. The vent pipe must be 4” single wall stainless steel (AL29-4C) or galvanized steel pipe of 26 minimum gauge. Maximum vent length is 15 feet (4.6 m) with two 90-degree elbows. Subtract 5 feet

from the total vent length for each additional 90-degree elbow used. No more than four 90-degree elbows may be used. Any short vertical portion of vent pipe used in the vent system shall be considered part of the allowable 15 feet (4.6 m) maximum run. Support the vent run at 4 foot intervals with overhead hangers. Horizontal sections of vent must rise ¼” for every foot of horizontal length. Any vent section greater than 45 degrees is considered an elbow.

Note: Single wall pipe should not be used in concealed, unoccupied or unheated locations. Listed thimbles or collars are necessary to pass through wall partitions. If the vent system passes through combustible areas where the vent clearance requirements cannot be maintained, it is permissible to chase straight sections of sealed 4 inch single wall vent through 5 inch (or greater) Type-B vent. The distance to combustibles using this chase technique is 1 inch. Note: Type-B vent should never be used as the actual vent system for the 125FX, as it is not gas tight.

Freeze Warning:

As mentioned on Page 5, negative air pressure in cold climates will cause a reverse airflow in the vent system that can freeze and damage the Aquastar heat exchanger when not in use. To prevent this the FXHOOD horizontal vent terminator, which was supplied separately with the water heater, needs to be installed on the end of the horizontal vent run (see page 8). The FXHOOD is a CSA approved vent terminator for the Aquastar 125FX and has a built in back draft flapper.

Flue Gas Sensor:

The 125FX is equipped with a Flue Gas Sensor; it’s mounted on the left side of the draft diverter (Flue Gas Sensor - #33 on page 19). Before leaving the installation site verify proper Flue Gas Sensor operation by temporarily blocking termination outlet. Once blocked then operate the heater, the unit should shut down within 1-3 minutes when the flue gases are blocked. You must reset the electrical power to the heater after this safety test has been conducted, otherwise the unit will not operate.

The flue gas exhaust temperature on the 125 FX is 356°F (180°C)

Venting Material

Exhaust vent

Exhaust vent maximum

Options

diameter

distance

 

 

 

Single wall stainless

 

15 feet (4.6 m) with two

steel (AL29-4C)

4 inch

elbows. Less 5 feet for

sealed vent pipe

 

each additional elbow.

Single wall galvanized

 

 

vent pipe (min. 26

 

15 feet (4.6 m) with two

gauge and sealed

4 inch

elbows. Less 5 feet for

with high temperature

 

each additional elbow.

silicone)

 

 

 

 

 

Clearances

from venting

material

Vent pipe within an

Vent pipe within an

unenclosed space

enclosed space

 

 

*See manufacturer's

*See manufacturer's

specifications

specifications

 

 

6 inches

NOT PERMISSIBLE

 

 

*Stainless steel (AL29-4C) vent pipe manufacturer's are Z-Flex, Protech and Heat Fab. The manufacturer's specified clearances are identified on the venting material. NOTE: clearance distances are variable depending if the vent pipe is installed in an enclosed or unenclosed space, the exhaust flue gas temperature and the orientation of the vent pipe.

6 720 606 601

7

Page 7
Image 7
AquaStar 125FX LP, 125FX NG specifications Venting, Feet 4.6 m with two

125FX NG, 125FX LP specifications

The AquaStar 125FX NG and 125FX LP are two remarkable models in the world of high-efficiency heaters. Designed for optimal performance in residential settings, these devices cater to diverse needs with their advanced technology and user-friendly features.

The AquaStar 125FX NG model operates using natural gas, while the 125FX LP utilizes liquid propane. This versatility allows users to choose the most suitable fuel type for their home setup. Both models boast an impressive energy efficiency rating, ensuring minimal energy waste while delivering reliable hot water on demand. This makes them not only cost-effective but also an eco-friendly choice for homeowners looking to reduce their carbon footprint.

One of the standout features of the AquaStar 125FX series is its compact design, which makes it ideal for installations in small spaces. With a sleek and modern appearance, it can easily blend into various interior aesthetics without occupying excessive room. The units are also relatively lightweight, facilitating a simple installation process.

In terms of performance, both the NG and LP models are equipped with a powerful BTU input that guarantees quick heating capabilities. They can provide ample hot water for multiple applications simultaneously, such as showers and dishwashing, making them perfect for busy households. Furthermore, the AquaStar 125FX units utilize advanced burner technology that ensures efficient combustion, resulting in a constant supply of hot water without fluctuations in temperature.

Safety is paramount in the design of the AquaStar 125FX series. Each heater is equipped with comprehensive safety features, including built-in vents for proper exhaust and a flame failure device that shuts the heater off if the flame goes out unexpectedly.

The control panel on both models is intuitive, allowing users to easily adjust the water temperature and monitor the unit's performance. Additionally, the AquaStar 125FX series is designed for longevity, with corrosion-resistant materials that withstand the rigors of daily use.

In summary, the AquaStar 125FX NG and 125FX LP are perfect examples of modern, efficient water heating technology. With their compact design, rapid heating capabilities, and robust safety features, these models present an excellent choice for any home looking to enhance its hot water supply while maintaining efficiency and environmental responsibility.