41
once
Factory
setting
DISPLAY
ACTION CONFIGURATION
x times
Section Digit 1 Digit 2 Digit 3 and 4
Stop pump after burner stops 4 0 0: no
1: yes
Pump speed 4 1 0: High speed
1: Adaptive
Pump post circulation duration 4 2 0to 5min by step
0.5 min
Inactive 4 3
Maximum Central Heating flow
temperature 4 4 50°to 85°
by steps of 1°
Minimum Central Heating flow
temperature 4 5 25°to 50°
by steps of 1°
Inactive 4 6
Inactive 4 7
CHanti-cycling delay 4 8 0to 7min by step
0.5 min
CH maximum output (range rating) 4 9 Value from 0to 10
Pmin & Pnominal
Menu - 4 - Boiler settings