Athena Technologies 16C instruction manual JMPØ2

Models: 16C

1 48
Download 48 pages 5.23 Kb
Page 20
Image 20

Input Menu

Input Menu (continued)

 

 

Input Jumper Settings

 

 

Display Parameter

Selection

 

 

 

 

 

 

 

 

Input Type

100 ohm

 

 

 

 

 

compressed RTD

 

 

 

 

 

0-20 mA

 

 

 

 

 

4-20 mA

 

 

 

 

 

0-10 mV

 

 

 

 

 

0-50 mV

 

 

 

 

 

0-100 mV

 

 

 

 

 

10-50 mV

 

 

 

 

 

 

 

 

 

 

0-1 V

 

Input Type

JMPØ1 JMPØ2

 

0-5 V

 

Thermocouple

Out

Out

JMPØ2

0-10 V

 

 

RTD

Out

Out

1-5 V

 

 

 

Voltage <100 mV

Out

Out

 

 

 

Voltage >100 mV

In

Out

 

 

 

Current Process

In

In

 

 

 

 

 

 

 

Note: When you ordered your controller, an input type was specified and the controller was set up accordingly and calibrated for that input type at the factory. If you decide to change input type from

thermocouple to RTD or vice-versa, you will need to recalibrate the controller unless you ordered the

JMPØ1

“Calibrate All” option. (Refer to page 56 for information on recalibration.) If you are changing from a temperature input type to a linear input type, you MUST recalibrate and change the jumper settings as indicated in the above table.

Input Menu

Temperature Input Type

Display Parameter

Selection

Bias (Display offset)

-100 to 100

Lower Setpoint Limit

Span of Sensor

Upper Setpoint Limit

Span of Sensor

Filtering

0.1-10.0 sec.

Linear Input Type

Display Parameter

Selection

Bias (Display offset)

-100 to 100

Low Scale

-1999 to 9999

High Scale

-1999 to 9999

Lower Setpoint Limit

Span of Sensor

Upper Setpoint Limit

Span of Sensor

Filtering

0.1-10.0 sec.

16

Page 20
Image 20
Athena Technologies 16C instruction manual JMPØ2