OnePower Line Interactive UPS (EN)
provide | expected | due to recent outage. | 2.If the battery is near the end | |
backup time. |
| 3.The UPS’s battery is near | of its service life, you have | |
|
|
| the end of its service life. | to replace the battery. |
|
|
|
|
|
The UPS operates | 1.Building wiring error such | 1.Call a qualified electrician in | ||
normally, | but | the | as missing ground or hot to | order to correct the building |
site wiring | fault | neutral wire reversal. | wiring. | |
indicator is lit. |
|
| ||
|
|
|
|
|
A.1.2 Upsilon2000
Situation | Solution | |
How | to install | Once started the UPS you can connect it to PC through |
the |
| cable. Now you can install UPSILON2000 on the PC. |
UPSilon2000. |
| |
PC | doesn’t 1.Check if the cable is properly connected | |
find the UPS. | 2.Use the original cable |
3.Launch Upsilon2000, then click on INSTALLATION and check that TYPE OF COMMUNICATION is correct (COM).
A.1.3 Battery and Input Circuit Breaker
Situation |
|
| Solution |
|
| |
Backup time |
| The battery backup time (sometime called battery reserve |
| |||
|
|
| time or battery autonomy) is the length of time the battery will |
| ||
|
|
| supply power to the load during a power failure. You can |
| ||
|
|
| check on the Appendix Backup Time. |
|
| |
Wich type of | 12VDC- 7A/h. |
|
| |||
battery | does |
|
|
|
| |
UPS use? |
|
|
|
|
| |
How often do I | Atlantis recommends to replace the batteries once a year. |
| ||||
have |
| to |
|
|
|
|
change |
|
|
|
|
|
|
battery? |
|
|
|
|
| |
Where | can | I | 1.please contact Your reseller. |
|
| |
find batteries? | 2.please contact directly Atlantis Land. |
|
| |||
|
|
|
|
| ||
How | can | I | Under | battery mode, when it¡soverload or short | circuit, |
|
check | the | UPS display UNUSUAL, then buzzer emits long sound |
| |||
Input | Circuit | for 30 | seconds, and automatically cut off output , | then it |
| |
Breaker? |
| should | be reset after eliminating fault. |
|
| |
|
|
|