| OnePower Line Interactive UPS |
| |
Technical Features |
|
|
|
| ||||
| Model |
|
|
|
|
| ||
| Power Rating(VA) | 650 |
|
| ||||
| Power Rating(W) | 375 |
|
| ||||
| INPUT |
| Voltage: |
|
|
| ||
|
|
| Frequency: |
| 50Hz±5% |
|
| |
| OUTPUT |
| Voltage: | 220V(±15%) [AC] / 220V(±10%) [INV] | ||||
|
|
|
|
|
|
|
|
|
|
|
| Frequency: |
| 50Hz (±1%) |
|
| |
|
|
| AVR |
|
|
| ||
|
|
| Waveform |
| Simulated SineWave |
|
| |
| TRANSFER Line/Battery |
| Less than 6 ms (typical) |
|
| |||
| EFFICIENCY |
|
| Total Efficiency Over 87% (AC to AC) | ||||
| BATTERY |
| Voltage |
| 12VDC |
|
| |
|
|
| Capacity |
| 12V/7.0Ah |
|
| |
|
|
| Quantity | 1 |
|
| ||
|
|
| Recharge Time |
|
|
| ||
|
|
| Type | Sealed Maintenance Free Lead Acid VRLA Type | ||||
| INDICATORS(4 LED) | Utility Normal, Backup, Battery Low and Fault | ||||||
|
|
|
|
|
| conditions |
|
|
| PROTECTION | Overload AC Buzzer continuously alarms for 30 | ||||||
|
|
|
|
| seconds, then Output is cut OFF and Input Circuit | |||
|
|
|
|
|
| Breaker change status |
|
|
|
|
|
|
| Overload Inverter Buzzer continuously alarms for | |||
|
|
|
|
| 30 seconds, then Output is cut OFF and Input | |||
|
|
|
|
| Circuit Breaker change status |
|
| |
|
|
|
|
| Short Circuit INV (Internal Fuse) |
|
| |
|
|
|
|
| Short Circuit AC(Input Circuit Breaker) | |||
|
|
|
|
| Battery | |||
|
|
|
|
| Low Warning & Cut Off(when battery descends to | |||
|
|
|
|
| 10VDC, UPS automatically cut off output) | |||
|
|
|
|
| Modem/Network RJ45 / RJ11 |
|
| |
|
|
|
|
|
| Spike Suppression |
|
|
|
|
|
|
|
| Noise Suppression |
|
|
| Audible Noise |
|
|
| <40 dBA |
|
| |
| CONNECTIONS | Output 2xIEC and 2XSchuko (Battery Power | ||||||
|
|
|
|
| Supplied) + 2xSchuko (Surge) |
|
| |
|
|
|
|
|
| Computer RS232 |
|
|
| Backup Time |
|
| Full Load approx 150s, Half Load apporx 550s | ||||
| MECHANICAL | Dimensions |
| 515 x 111 x 91 mm |
|
| ||
|
|
|
| (WxHxD): |
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
| Pag. 42 |