12 Stove Installation (for qualified installers only)
Travis Industries 100-01140 4020628
Alcove Installation Requirements
Whenever the stove is placed in a location where the ceiling height is less than 7' tall, it is considered
an alcove installation. Because of the reduced height, the special installation requirements listed
below must be met.
Chimney connector and chimney must be one of the following types:
DURAVENT model DVL with DURATEC chimney
DURAVENT model DVL with DURA-PLUS chimney
AMERI-TEC model DCC with model HS chimney
SECURITY model DL with SECURITY model ASHT or S2100 chimney
METAL-FAB model DW with TG chimney
GSW Double Wall Chimney Connector with Super Chimney Twenty-One
SELKIRK METALBESTOS model DS connector with model SSII chimney
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
Standard Masonry Chimney with any one of the above listed connectors

Rainier-45°Rainier-90°

Minimum Clearance

(See the illustration below) Combustible
Alcove Non-Combustible
Alcove Combustible
Alcove Non-Combus tible
Alcove
A Sidewall to stove 16" 6" 14" 6"
B Backwall to stove 14" 4" 9 1/2" 2"
D Connector to sidewall 25 1/2" 15 1/2" 23 1/2" 15 1/2"
E Connector to backwall 10" 2" 10 1/4" 2 3/4"
G Maximum depth of alcove 48" 48" 48" 48"
H Minimum width of alcove 57 3/4" 37 3/4" 53 3/4" 37 3/4"
J Minimum height of alcove 84" 6" above stove top 84" 6" above stove top
Alcoves are classified as combustible or non-combustible. Non-combustible alcoves must have
walls and a ceiling that are 3 1/2" thick of a non-combustible material (brick, stone, or concrete).
This non-combustible material must be spaced and ventilated at least 1" off of all combustible
materials (walls, ceiling, etc.) to allow air to move around the non-combustible walls and ceiling.
All other alcoves are considered combustible. The clearances below must be met:
Non-combustible alcove
construction (on walls
and ceiling) - see the
explanation above.
3 1/2" thick non-
combustible
material
Combustible
materials
1" Min.
Ventilated
air space
Non-combustible
reinforcer
a
b
de
h
j