AXIS Electrical Safety Kit A/B Page 7

ENGLISH

Connection Diagram

If an external protective bonding wire is used it is recom-
mended to have a miminum area of 6mm2 (AWG 10) for indoor
use and a minimum area of 10mm2 (AWG 8) for outdoor use.
The circuitry shall be connected to an external double pole cir-
cuit breaker in the building installation.
The door switch shall only be used for signal voltage (SELV) and
shall not be connected to the mains voltage or power supply.
1 MCB fuse 4A (circuit breaker) L Line
2 Incoming mains voltage N Neutral
3 Surge protector PE Protective earth (ground)
4 To power supplies Ground
5 Door switch
CIRCUIT BREAKER/
FUSE 4 A
DOOR SWITCH
EXTERNAL PROTECTIVE
BONDING WIRE
L
N
L1
N1
N
PE PE1
LSURGE PROTECTOR
230 V AC
or
120 V AC
TO
POWER
SUPPLIES
INCOMING
MAINS VOLTAGE
TT - TNS - TNC - IT
1532 4