AXIS Electrical Safety Kit A/B Page 9
ENGLISH
Install the Devices
The electrical connections and conduit installations shall be
made by a certified electrician and in compliance with local
regulations.
Risk of electric shock. The mains supply shall be disconnected
during installation.
Keep the wires short but do not stretch them. Short wires give
better surge protection than long wires.
The ground wire should be as short as possible and have as
large cross section as possible. Attach the ground wire to a
suitable grounding point, for example an earth stake.
1. Snap on the fuse, surge protector and terminal blocks on the DIN
rail. See Hardware Overview, on page 6 and the examples on
page10. Make sure that the positi ons correspond to the slots in the
device cover.
See the User Guide provided with the surveillance cabinet for more
information about the device cover.
2. Connect the devices according to the connection diagram. See
page7. Use a cable of minimum 2.5 mm2 (AWG 14) for incoming
mains voltage.
3. Secure the cables. Use 2.8Nm (25 lb-in) torque for the screw
terminals.
4. Attach the device cover to the cabinet base according to the
instructions provided with the surveillance cabinet.