2. System Overview
Image 2-13
Identification
2. In case of overload, the thermal-magnetic protection in the control panel shall be switched off after a short period of time. Check
the load, reduce it if necessary and switch on the thermal-magnetic protection again.
3. In case of short-circuit, the thermal-magnetic protection will switch off immediately! Check what caused the short-circuit and
switch on the protection again afterwards.
Image 2-14
Main breaker
CAUTION:Never let the diesel engine run for longer periods (> 30 min) without charge or small loads (< 15%).
This could result in severe damage to the diesel engine.
2.5.5 Stopping the generator
How to stop
1. Let the generator run at no load for a few more minutes before stopping it. In this way the generator can "cool down".
2. Stop the generator with the starting key.
2.5.6 About cooling the generator
Attention points
• Make sure there are no obstructions at the fresh air intake grid where the cooling air for engine and alternator comes in.
• Make sure the hot air that comes from cooling the engine and alternator can leave easily through the grid, as well as the exhaust
gases.
• Never let the generator run in an inappropriately ventilated room!
2.5.7 Protections
Engine
Low oil pressure protection and high cooling water temperature protection.
18 R5976956 B-10 MOBILE LED 19/06/2007