Bard 357-93-E manual Cooling Application Data - Outdoor Temperature, Capacity Multiplier Factors

Models: 357-93-E

1 12
Download 12 pages 51.81 Kb
Page 10
Image 10
Cooling Application Data - Outdoor Temperature 1

Cooling Application Data - Outdoor Temperature 1

Model

D.B./W.B.

Cooling

75oF

80oF

85oF

90oF

95oF

100oF

105oF

110oF

115oF

120oF

125oF

2

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

75/

Total Cooling

19,600

18,675

17,725

16,825

15,925

15,050

14,175

13,325

12,500

11,700

11,100

 

62

Sensible Cooling

14,825

14,700

14,475

14,190

13,830

13,390

12,880

12,300

11,640

10,700

10,150

WL182

80/

Total Cooling

20,975

20,360

19,710

19,020

18,300

17,540

16,750

15,920

15,060

14,400

13,800

67

Sensible Cooling

14,625

14,465

14,300

14,135

13,970

13,640

13,230

12,720

12,125

11,600

11,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

24,950

23,780

22,620

21,460

20,315

19,180

18,050

16,930

15,815

14,700

13,600

 

72

Sensible Cooling

14,750

14,620

14,400

14,090

13,690

13,190

12,610

11,930

11,155

10,400

9,650

 

75/

Total Cooling

24,900

23,880

22,870

21,670

20,880

19,900

18,920

17,960

17,000

16,050

15,050

 

62

Sensible Cooling

19,900

19,530

19,140

18,720

18,275

17,800

17,300

16,770

16,215

15,300

14,300

WL242

80/

Total Cooling

26,600

26,040

25,420

24,740

24,000

23,210

22,350

21,450

20,480

19,000

17,550

67

Sensible Cooling

19,300

19,160

18,970

18,740

18,460

18,140

17,770

17,350

16,890

15,700

14,400

 

 

85/

Total Cooling

31,300

30,350

29,260

28,020

26,640

25,110

23,440

21,620

20,600

19,475

18,400

 

72

Sensible Cooling

19,775

19,430

19,040

18,590

18,090

17,530

16,920

16,260

15,540

14,700

13,900

 

75/

Total Cooling

23,400

22,600

21,800

21,000

20,100

19,200

18,300

17,400

16,400

15,400

14,300

 

62

Sensible Cooling

19,100

18,700

18,400

17,900

17,600

17,100

16,600

16,200

15,600

15,100

14,600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL253

80/

Total Cooling

24,900

24,600

24,200

23,700

23,000

22,300

21,500

20,700

19,700

18,600

17,400

67

Sensible Cooling

18,500

18,300

18,200

17,900

17,700

17,400

17,000

16,700

16,200

15,800

15,300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

29,700

28,800

27,800

26,800

25,600

24,400

23,200

22,100

20,700

19,400

17,900

 

72

Sensible Cooling

19,000

18,600

18,300

17,800

17,400

16,900

16,200

15,700

15,000

14,300

13,600

 

75/

Total Cooling

30,900

29,700

28,500

27,400

26,100

25,100

24,000

22,900

21,900

20,800

19,700

 

62

Sensible Cooling

25,700

25,300

24,900

24,400

23,900

23,300

22,700

22,200

21,500

20,800

20,100

WL302

80/

Total Cooling

33,000

32,300

31,600

30,900

30,000

29,200

28,300

27,300

26,300

25,200

24,000

67

Sensible Cooling

24,900

24,800

24,600

24,400

24,100

23,700

23,300

22,900

22,300

21,700

21,100

 

 

85/

Total Cooling

39,300

37,800

36,300

34,900

33,400

32,000

30,500

29,100

27,700

26,200

24,700

 

72

Sensible Cooling

25,500

25,200

24,700

24,300

23,700

23,000

22,200

21,500

20,600

19,600

18,700

 

75/

Total Cooling

37,300

35,700

34,200

32,800

31,400

30,100

28,900

27,800

26,700

25,700

24,600

 

62

Sensible Cooling

28,100

27,700

27,300

26,800

26,400

25,800

25,200

24,500

23,800

22,900

22,100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL372

80/

Total Cooling

39,800

38,900

38,000

37,000

36,000

35,100

34,100

33,100

32,100

31,100

30,000

67

Sensible Cooling

27,200

27,100

27,000

26,800

26,600

26,200

25,800

25,300

24,700

24,000

23,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

47,400

45,500

43,700

41,800

40,000

38,400

36,800

35,200

33,800

32,300

30,900

 

72

Sensible Cooling

27,900

27,500

27,200

26,600

26,100

25,400

24,600

23,700

22,800

21,700

20,600

 

75/

Total Cooling

43,200

41,700

40,100

38,400

36,600

34,800

33,000

31,000

29,000

26,900

24,700

 

62

Sensible Cooling

35,000

34,300

33,500

32,800

32,000

31,200

30,200

29,300

28,300

27,200

26,100

WL423

80/

Total Cooling

46,100

45,400

44,500

43,400

42,000

40,500

38,900

37,000

34,900

32,600

30,100

67

Sensible Cooling

33,900

33,600

33,200

32,800

32,300

31,700

31,000

30,300

29,400

28,500

27,500

 

 

85/

Total Cooling

54,900

53,100

51,100

49,000

46,700

44,300

42,000

39,400

36,700

33,900

31,000

 

72

Sensible Cooling

34,700

34,100

33,400

32,600

31,700

30,700

29,600

28,400

27,100

25,800

24,400

 

75/

Total Cooling

48,200

46,300

44,650

43,070

41,300

39,340

37,190

34,840

32,300

30,900

29,500

 

62

Sensible Cooling

39,120

38,520

37,680

37,510

37,000

36,130

34,910

33,330

31,400

30,000

28,700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL484

80/

Total Cooling

51,440

50,440

49,640

48,750

47,500

45,890

43,920

41,590

38,900

38,100

37,250

67

Sensible Cooling

37,950

37,800

37,600

37,400

37,300

36,740

35,800

34,490

32,800

32,050

31,350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

59,900

58,650

57,240

55,350

52,700

49,700

46,700

43,800

40,850

39,100

37,450

 

72

Sensible Cooling

38,750

38,250

37,450

37,230

36,600

35,570

34,150

32,320

30,100

28,700

27,500

 

75/

Total Cooling

60,350

57,500

54,630

52,320

50,000

47,660

45,290

42,910

40,500

N/A

N/A

 

62

Sensible Cooling

45,170

43,700

42,180

41,110

40,000

38,840

37,640

36,390

35,100

N/A

N/A

WL602

80/

Total Cooling

64,600

62,750

60,690

59,190

57,500

55,610

53,540

51,260

48,800

N/A

N/A

67

Sensible Cooling

43,950

42,960

41,830

41,150

40,400

39,570

38,660

37,670

36,600

N/A

N/A

 

 

85/

Total Cooling

76,800

73,300

69,610

66,740

63,800

60,780

57,700

54,530

51,300

N/A

N/A

 

72

Sensible Cooling

44,900

43,470

41,970

40,840

39,600

38,260

36,810

35,260

33,600

N/A

N/A

 

75/

Total Cooling

66,200

63,600

61,000

58,400

55,700

53,200

50,700

48,100

45,500

N/A

N/A

 

62

Sensible Cooling

50,600

47,900

45,400

43,500

42,000

40,800

40,100

39,600

39,500

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WL702-A

80/

Total Cooling

70,700

69,300

67,700

66,000

64,000

62,000

59,800

57,400

54,800

N/A

N/A

67

Sensible Cooling

49,100

46,900

45,000

43,500

42,400

41,500

41,100

40,900

41,100

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

84,200

81,000

77,700

74,500

71,100

67,800

64,500

61,100

57,600

N/A

N/A

 

72

Sensible Cooling

50,300

47,600

45,200

43,200

41,600

40,200

39,200

38,400

37,900

N/A

N/A

 

75/

Total Cooling

69,700

66,800

63,900

61,100

58,300

55,550

52,800

50,150

47,500

N/A

N/A

 

62

Sensible Cooling

49,500

48,000

46,600

45,300

44,000

42,800

41,600

40,550

39,500

N/A

N/A

WL701-B,C

80/

Total Cooling

74,550

72,850

71,050

69,100

67,000

64,800

62,400

59,900

57,250

N/A

N/A

67

Sensible Cooling

48,050

47,100

46,200

45,300

44,450

43,600

42,750

41,950

41,150

N/A

N/A

 

 

85/

Total Cooling

88,700

85,100

81,550

77,950

74,400

70,800

67,250

63,650

60,100

N/A

N/A

 

72

Sensible Cooling

49,150

47,750

46,350

44,950

43,550

42,134

40,700

39,300

37,850

N/A

N/A

1Below 65oF (18.3C), unit requires a factory or field installed low ambient control.

2 Return air temperature.

Capacity Multiplier Factors

% of Rated Airflow

-10

Rated

+10

 

 

 

 

Total BTUH

0.975

1.0

1.02

Sensible BTUH

0.950

1.0

1.05

Form No.

S3279-206

Supersedes

S3279-106

Page

10 of 12

Page 10
Image 10
Bard 357-93-E manual Cooling Application Data - Outdoor Temperature, Capacity Multiplier Factors